Siemens MICROMASTER 440 Quick Start Manual page 66

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 08/03
Fault
/
Description
Warning
Warning
A0511
Motor Over
temperature Warning
A0541
Motor Identification
Active
A0910
VDC Max Controller
Deactivated Warning
A0911
VDC Max Controller
Active Warning
A0920
Analog Input
Parameters Incorrect
Warning
A0921
Analog Output
Parameters Incorrect
Warning
A0922
No Load Applied to
Inverter Warning
A0923
Jog Left and Jog Right
Applied Warning
66
Cause / Remedy
Motor power (P0307) must match inverter power (r0206)
Load duty cycle must be correct
Check if name plate data are correct (if not perform quick
commissioning)
Accurate equivalent circuit data can be found by performing motor
identification (P1910=1)
Check if motor weight (P0344) is reasonable. Change if necessary
Check if temperature shown in r0035 is reasonable
Motor data identification (P1910) selected or running
Occurs if line supply voltage (compared to P0210) is permanently
too high
Occurs if motor is driven by an active load, causing motor to go into
regenerative mode Occurs at very high load inertias, when ramping
down
Vdc max controller is active; so ramp-down times will be increased
automatically to keep DC-link voltage (r0026) within limits (P2172).
AIN parameters incorrect – check that they are not set to identical
values.
Check that parameters are logical for AIN type.
AOUT parameters are incorrect. Check that settings are not
identical to each other.
No Load is applied to the inverter – (Motor not connected) - Check
wiring to motor.
Both JOG right and JOG left (P1055/P1056) have been requested.
This freezes the RFG output frequency at its current value.
Quick Start Guide
MICROMASTER 440
6SE6400-5GA00-0BP0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mm440

Table of Contents