Siemens MICROMASTER 440 Quick Start Manual page 41

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

3-Wire Control (Using Relay 1 for Latching)
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
P0003=2 (Extended)
P0700[0]=2 (Terminals)
P0701[0]=1 (DIN1=Start)
P0702[0]=3 (DIN2=OFF2)
P0731=52.2 (Drive Running)
NOTE:
This method works by locking
in the START signal using a
relay.
Hand Off Auto (HOA)
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
P0003=3 (Expert)
P0700[0]=2 (Auto/OFF)
P0700[1]=1 (Hand)
P0700[2]=2 (Auto)
P0701[0,1,2]=99 (BICO)
P0702[0,1,2]=0 (disabled)
P0703[0,1,2]=99 (BICO)
P0704[0]=0 (disabled)
P0704[1]=0(disabled)
P0704[2]=1 (Run/Stop)
P0810=722.0 (DIN1-Hand)
P0811=722.2 (DIN3-Auto)
P1000[0]=2 (AIN1)
P1000[1]=1 (BOP/MOP)
P1000[2]=2 AIN1)
MICROMASTER 440
6SE6400-5GA00-0BP0
Wiring when
Relay 1 performs
the "latching"
process
STOP
Normally Closed Push
Button (Momentary Action)
START
Normally Open Push
Button (Momentary Action)
DIP SW 1
DIP SW 2
(Analog Input 1)
(Analog Input 2)
ON (UP) = 0 to 20mA
ON (UP) = 0 to 20mA
OFF = 0 to 10V
OFF = 0 to 10V
HAND =
BOP – RUN/STOP
BOP – Setpoint
AUTO =
DIN4 – RUN/STOP
AIN1 = Setpoint
Quick Start Guide
RL1
RL1
RL1
RL2
NC
NO
COM
NO
A
A
A
OUT1
OUT1
PTC
PTC
DIN
DIN
OUT2
+
-
A
B
5
6
+
AIN1
AIN1
DIN
DIN
DIN
10V 0V
+
-
1
2
3
RL1
RL1
RL1
NC
NO
COM
A
A
OUT1
OUT1
PTC
PTC
DIN
DIN
OUT2
+
-
A
B
5
6
AIN1
AIN1
DIN
DIN
10V
0V
+
-
1
2
0 – 20mA or
4 – 20mA
3 Position Switch
Issue 08/03
RL2
RL3
RL3
RL3
COM
NC
NO
COM
A
OUT2
Iso
P
N
-
0V
+
-
DIN
Iso
AIN2
AIN2
4
24V
+
-
STOP
START
RL2
RL2
RL3
RL3
RL3
NO
COM
NC
NO
COM
A
A
OUT2
Iso
P
N
+
-
0V
+
-
DIN
DIN
Iso
AIN2
AIN2
3
4
24V
+
-
41