5.8.2 Analog inputs (ADC)
Parameter range
Features:
Quantity
Cycle time
Resolution
Accuracy
Electrical features
Function chart number
Analog signals are converted to digital signals inside the drive using Analog to Digital Converters.
The user must select either Voltage (default) or Current using the 2 switches on the I/O board
DIP1(1,2). Additionally, P0756 must also be set accordingly.
Example using voltage input
DIP SW 1
(Analog Input 1)
ON (UP) = 0 to 20mA
OFF = 0 to 10V
Possible settings of P0756:
0 Unipolar voltage input ( 0 to 10 V )
1 Unipolar voltage input with monitoring (0 to 10 V )
2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
4 Bipolar voltage input (-10 V to +10 V) (only AIN1)
MICROMASTER 440
6SE6400-5GA00-0BP0
Table 5-7 Analog Input Specifications
DIP SW 2
(Analog Input 2)
ON (UP) = 0 to 20mA
OFF = 0 to 10V
Figure 5-8 DIP Switch And P0756 for Analog Voltage Input
Quick Start Guide
P0750 – P0762
2
4 ms
10 bits
1% of full scale (10V or 20mA)
Polarity protection, short-circuit proof
FP2200 (in parameter list)
RL1
RL1
RL1
NC
NO
COM
A
A
OUT1
OUT1
PTC
PTC
DIN
DIN
+
-
A
B
5
6
AIN1
AIN1
DIN
DIN
10V
0V
+
-
1
≥ 4.7k Ω
RL2
RL2
RL3
RL3
RL3
NO
COM
NC
NO
COM
A
A
OUT2
OUT2
Iso
P
N
+
-
0V
+
-
DIN
DIN
Iso
AIN2
AIN2
2
3
4
24V
+
-
≥ 4.7k Ω
Issue 08/03