Prot - gefran 1600 Installation And Operation Manual

Table of Contents

Advertisement

rl. o . 1
Out 1
Allocation of
reference signal:
67
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs
rl. o . 2
Out 2
Allocation of
reference signal:
68
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs
rl. o . 3
Out 3
Allocation of
reference signal:
69
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs
rl. o . 4
Out 4
Allocation of
reference signal:
70
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs
(t. 1
Cycle time for
-
MAIN relay or
logic output =
HEAT or COOL
71
(t. 2
Cycle time for AL1
-
relay or logic
output = HEAT or
COOL
72
Cycle time for AL2
(t. 3
-
relay or logic
output = HEAT or
COOL
73
Cycle time for AL3
(t. 4
-
relay or logic
output = HEAT or
COOL
74
rel.
Fault action (sets state in
-
case of probe fault) Alarm
outputs AL1, AL2, AL3;
75
Select intrinsic safety
Note:
1) In case of broken probe, logic state of individual alarm assumes
selected logic value without consideration of alarm type (direct or
inverse): ON=alarm active;
OFF=alarm inactive
2) Assign alarms to available outputs by entering codes rLo1, rLo2,
rLo3, rLo4.
80080D_MHW_1600-1800_0308_ENG
rL.o.1, rL.o.2, rL.o.3, rL.o.4
rL.o.x
Function of main output relay/logic (OUT1)
0
HEAT (control output for heating)
1
COOL (control output for cooling)
2
AL1 - alarm 1
3
AL2 - alarm 2
4
AL3 - alarm 3
5
AL.HB - alarm HB
6
LBA - alarm LBA
7
IN1 - repetition of logic input 1
8
IN2 - repetition of logic input 2
9
-
10
-
11
-
12
Repeat Timer
13
Repeat Set / Reset
14
(AL1) OR (AL2)
15
(AL1) OR (AL2) OR (AL3)
16
(AL1) AND (AL2)
17
(AL1) AND (AL2) AND (AL3)
18
(HBAL) OR (AL1)
19
(HBAL) OR (AL1) OR (AL2)
20
(HBAL) AND (AL1)
21
(HBAL) AND (AL1) AND (AL2)
+ 32 for inverse logic signal output
64
Heat control output with
fast cycle time (*)
65
Cool control output with
fast cycle time (*)
(*) only for rL.o.1.; HB alarm is disabled if
associated with Out1 output
1 ... 200 sec
(0.1 ... 20.0 sec)
1 ... 200 sec
1 ... 200 sec
1 ... 200 sec
_rEL. Alarm
Alarm
1
2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
OFF
OFF
5
ON
OFF
6
OFF
ON
7
ON
ON
an. o . 1
78
+ 16 for inverted output with respect to reference value
+ 32 for output with 2...10V, 4...20mA signal
(*) - Fixed scale limits
l. a n. 1
76
x. a n. 1
77
an. o . 2
81
l. a n. 2
79
x. a n. 2
80
Alarm
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON

Prot

42
Prot
0
1
2
3
+ 4 to disable InP, Out
+ 8 to disable CFG, Ser,
+ 16 to disable SW "power-up - power down"
+ 32 disable manual power latching
+ 64 to disable manual power modification
Out W1
Assignment of signal or reference value: PV, SP,
SP-PROG, DEV+, DEV-, IN.AUX, HEAT, COOL,
AL1, AL2, AL3, serial line value
An.o.1, An.o.2
An.o.x Reference value
0
PV - process variable
1
SSP - active setpoint
2
SP - local setpoint
3
InP.2 - aux input
4
Deviation (SSP-PV)
5
HEAT
(*)
6
COOL
(*)
7
AL1 (alarm point)
8
AL2 (alarm point)
9
AL3 (alarm point)
10
AL.HB - (alarm point)
11
Value acquired from serial line
- Retransmission output not available with ON/OFF control action
Minimum limit of
-100.0...100.0% for power
analogue repetition
-1999...9999 for inputs and setpoint
signal output 1
Maximum limit of
-100.0...100.0% for power
analogue repetition
-1999...9999 for inputs and setpoint
signal output 1
Out W2.
Assignment of signal or reference value: PV, SP,
SP-PROG, DEV+, DEV-, IN.AUX, HEAT, COOL,
AL1, AL2, AL3, serial line value
Minimum limit of
-100.0...100.0% for power
analogue repetition
-1999...9999 for inputs and setpoint
signal output 2
Maximum limit of
-100.0...100.0% for power
analogue repetition
-1999...9999 for inputs and setpoint
signal output 2
• Prot
Protection code
Display
SP, InP2, alarms, OutP, INFO, DATA
SP, InP2, alarms, OutP, INFO, DATA
SP, InP2, alarms, OutP, INFO
SP
Modification
SP, alarms, DATA
SP, alarms
SP
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1800

Table of Contents