Vega POINTRAC 31 Operating Instructions Manual page 47

Radiation-based sensor for level detection
Table of Contents

Advertisement

Process conditions
For the process conditions, please also note the specifications on the type label. The lower value
always applies.
Process pressure
Process temperature (measured on the
detector tube)
Vibration resistance
3)
Electromechanical data - version IP 66/IP 67
Cable entry
Ʋ M20 x 1.5
Ʋ ½ NPT
Spring-loaded terminals for wire cross-section
Ʋ Massive wire, cord
Ʋ Stranded wire with end sleeve
Display and adjustment module
Display element
Measured value indication
Ʋ Number of digits
Ʋ Size of digits
Adjustment elements
Protection rating
Ʋ unassembled
Ʋ mounted into the housing without
cover
Material
Ʋ Housing
Ʋ Inspection window
Integrated clock
Date format
Time format
Time zone Ex factory
Measurement electronics temerature
Resolution
Accuracy
Tested according to the guidelines of German Lloyd, GL directive 2.
3)
POINTRAC 31 • 8/16 mA/HART - four-wire
Unpressurized
-40 ... +60 °C (-40 ... +140 °F)
With temperatures of more than 60 °C we recommend
the use of water cooling
mechanical vibrations up to 1 g in the frequency range
5 ... 200 Hz
2 x cable gland M20 x 1.5 (cable: ø 6 ... 12 mm), 4 x
blind plug M20 x 1.5
Included: 1 x cable gland M20 x 1.5
5 x closing cap (red) ½ NPT
Included: 3 x cable gland ½ NPT (cable: ø 6 ... 12 mm),
4 x blind plug ½ NPT
0.2 ... 2.5 mm² (AWG 24 ... 14)
0.2 ... 1.5 mm² (AWG 24 ... 16)
Display with backlight
5
W x H = 7 x 13 mm
4 keys
IP 20
IP 40
ABS
Polyester foil
Day.Month.Year
12 h/24 h
CET
1 °C (1.8 °F)
±1 °C (1.8 °F)
11 Supplement
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents