Electrical Specifications
Notification Appliance Circuits and Releasing Circuits
Max. wiring voltage drop
NAC Nominal operating
voltage
Special Applications for
Releasing Circuits
Current for all external
devices connected to the
control panel's power supply
Optional ACPS-2406
Optional ACPS-610
Optional APS-6R
Maximum signaling
current/circuit per NAC
End-of-Line Resistors
(ELRs)
NOTE: For a list of compatible Notification Appliance Circuits and Releasing Circuits see Notifier Device
Compatibility Document 15378.
Output Relays (common)
Output relays for Alarm and Trouble are common on TB4; Supervisory, and Security are program-
mable on TB5. See Figure 3.11, "Form-C Relay Connections" on page 27).
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB10 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
Nominal voltage: 24 VDC special applications.
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB10 NONRESET (+) and (–) supply one (1) power-limited circuit avail-
able to power external devices, such as notification appliances and annunciators.
Nominal voltage: 24 VDC regulated, special applications, 1.5 A max.
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
TB10, TB2, and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible devices and notification appliances.
NOTE: The Control Panel provides a total of 7.4 A of power in alarm (3.9 A in standby), shared
by all internal circuitry and external provisions (24 V resettable and non-resettable). TB10 and all
4 NACs share a maximum of 3.0 A in standby and 6.0 in alarm. For power requirements, refer to
the power supply calculation tables in Appendix A.
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Item
2 VDC
(Retrofit note: SLCs with old CMX modules are restricted to 1.2 VDC.)
24 VDC regulated; 1.5 A max.
20.16 - 26.42 VDC
7.4 A in alarm (3.9 A continuous)
TB10 and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Total 6 A in alarm (5 A continuous)
Total 6 A in alarm (1.5 A single output)
Total 6 A in alarm (4 A continuous)
1.5 A
Note: Some devices have maximum draws less than this; refer to the device's
documentation.
Control Panel NACs (TB6, TB7, TB8, TB9): 2.2K, 1/2 watt
XP6-C, FCM-1 Modules: 47K, 1/2 watt
Electrical Specifications
Value
59