Scope Of Delivery - Gossen MetraWatt SECUTEST PRO Manual

Test instruments for measuring the electrical safety of devices
Hide thumbs Also See for SECUTEST PRO:
Table of Contents

Advertisement

Overview of Features Included with
SECUTEST BASE(10) and PRO Test Instruments
Measuring Function
Test Current/Voltage
Single measurements, rotary switch level: green
R
R
Protective conductor resistance
PE
PE
I
Test current (200 mA)
P
SECUTEST BASE10/PRO: 10 A
Section
(feature G01)
8.5
R
R
Insulation resistance (PC I/PC II)
ISO
ISO
U
Test voltage
ISO
Section
8.6
I
I
Protective conductor current, RMS
PE
PE
I
AC component
PE~
Section
I
DC component
PE=
8.7.1
U
Test voltage
LN
I
I
Touch current, RMS
B
B
I
AC component
B~
Section
I
DC component
B=
8.7.2
U
Test voltage
LN
I
I
Device leakage current, RMS
G
G
I
AC component
G~
Section
I
DC component
G=
8.7.3
U
Test voltage
LN
I
I
Leakage current from the applied part, RMS
A
A
Section
U
Test voltage
A
8.7.4
I
I
Patient leakage current, RMS
P
P
I
AC component
P~
Section
I
DC component
P=
8.7.5
U
Test voltage
LN
U
U
Probe voltage, RMS
U
Alternating voltage component
~
U
Direct voltage component
=
U
Measuring voltage, RMS
U
Alternating voltage component
~
Section
U
Direct voltage component
=
8.9
ta
4
ta
PRCD time to trip for 30 mA PRCDs
Section
U
Line voltage at the test socket
LN
8.10
P
Function test at the test socket
I
Current between L and N
U
Voltage between L and N
f
Frequency
P
Active power
Section
S
Apparent power
8.11
PF
Power factor
Probe Measuring Functions
EL1
Extension cord with adapter: continuity, short-circuit,
Section
polarity (wire reversal)
8.12
EXTRA
Reserved for expansion during the course of software updates
Section 9
°C
Temperature measurement
Pt1000
1
10 A R
measurements are only possible with line voltages of 115/
PE
230 V and line frequencies of 50/60 Hz.
2
Voltage measuring inputs with SECUTEST PRO only (or instrument with
feature I01)
3
nd
Connection for 2
test probe for 2-pole measurement with SECUTEST
PRO only (or instrument with feature H01)
4
Measurement of time to trip is not possible in IT systems.
GMC-I Messtechnik GmbH
Measurement
Type, Connection
Type
PE(TS) - P1 passive
PE(TS) - P1 active
PE(mains) - P1
1
PE(mains) - P1 clamp
3
P1–P2
LN(TS) - PE(TS)
LN(TS) - P1
3
P1–P2
PE(mains) - P1
PE(TS) - P1
LN(TS) - P1//PE(TS)
Direct
Differential
Alternative
2
AT3-Adapter
2
Clamp
Direct
Differential
Alternative (P1)
Perm. connection
Alternative (P1–P2)
Direct
Differential
Alternative
2
AT3-Adapter
2
Clamp
Direct (P1)
Alternative (P1)
Perm. con. (P1)
Direct (P1)
Perm. con. (P1)
P1–P2
P1–P2 (with mains*)
* Polarity param.
2
2
V – COM
V – COM (with mains)
2
Polarity parameter
EL1 adapter
AT3-IIIE adapter
VL2E adapter
2
with Pt100 /
V – COM
Key
Alternative
= alternative measurement (eq. leakage current meas.)
Differential = differential current measurement
Direct
= direct measurement
LN(TS)
= short-circuited L and N conductors at test socket
P1
= measurement with test probe P1
P1-P2
= 2-pole measurement with test probes P1 and P2
PE-P1
= measurement between PE and test probe P1
PE(TS)
= protective conductor at the test socket
PE(mains)
= protective conductor at the mains connection
2
Standard
Automated test sequences, rotary switch level: orange
Preconfigured (freely adjustable) test sequences – default settings
A1
VDE 0701-0702
A2
VDE 0701-0702
A3
VDE 0701-0702-EDV
A4
IEC 62353 (VDE 0751)
A5
IEC 62353 (VDE 0751)
A6
IEC 60974-4
A7
IEC 60974-4
A8
VDE 0701-0702
AUTO
VDE 0701-0702
Differences with Regard to Included Features
Feature
SECUTEST BASE SECUTEST BASE10 SECUTEST PRO
10 A RPE test current
Touch-screen keyboard
nd
2
test probe
Voltage meas. inputs *
Database expansion
* For voltage measurement or for connecting a WZ12C current clamp or
an AT3 adapter, and for temperature measurement via RTD

Scope of Delivery

Standard Version (country-specific)
1 SECUTEST BASE(10) or PRO test instrument
1 Mains power cable
1 Test probe, 2 m, not coiled
1 USB cable, USB A to USB B, 1.0 m long
1 Plug-on alligator clip
1 KS17-ONE cable set for voltage measuring input
(only with SECUTEST PRO or instrument with feature I01)
1 Calibration certificate
1 Condensed operating instructions
1 Comprehensive operating instructions available on the Inter-
net
1 ETC report software available on the Internet
The most up-to-date version of ETC report generating software
can be downloaded free of charge from the mygmc page of our
website as a ZIP file, if you have registered your test instrument:
http://www.gossenmetrawatt.com
→ Products → Software → Software for Testers → Report Soft-
ware without Database → ETC →
!
Attention!
The following must be observed if other software packages are
used: ETC report generating software must first be in-
stalled to the PC in order to be able to read out data with
the help of other software packages such as PC.doc-
WORD/EXCEL, PC.doc-ACCESS, ELEKTRO manager and PS3.
Measurement Type, Connection Type
Passive measurement type, test socket
Active measurement type, test socket
Parametrization for EDP (active)
Active measurement type
Active measurement type
Connection type: test socket
Connection type: AT16-DI/AT32-DI
Extension cord measurement type (RPE, RISO), adapter:
EL1/VL2E/AT3-IIIE
Active measurement type, test socket
myGMC
3

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SECUTEST PRO and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Secutest base 10

Table of Contents