General Specifications - Pepperl+Fuchs 6000 SERIES Installation And Operation Manual

Purge/pressurization system
Hide thumbs Also See for 6000 SERIES:
Table of Contents

Advertisement

6000 Series Purge/Pressurization System

General specifications

Enclosure volume:
Number of volume exchange:
Hazardous environment:
Operation mode for purging (rapid exchange valve)
STD:
SA:
Manually ON, automatically OFF
FA:
Electrical parameters
6000 series control unit
Power requirement:
AC version:
100 to 250 VAC/ 50-60 Hz / 0.2 A
DC version:
Fuse replacement - power:
AC version:
3.15 A Slo-Blo fuse, 5 x 20 mm size
DC version:
2.0 A Slo-Blo fuse, 5 x 20 mm size
Type of fuse:
UL recognized, JDYX2 / JDYX8 type
Outputs:
ENC_1, ENC_2
Protected enclosure contacts:
(Dry contacts (2) SPST N.O.)
AUX1 (output 1)
Auxiliary 1 contact output:
(Dry contacts, SPDT)
AUX2 (output 2)
Auxiliary 2 contact outputs:
(Dry contacts, SPDT)
Fuse replacement - AUX contacts
AUX1, AUX 2:
2.0 A Slo-Blo fuse, 5 x 20 mm size
Inputs:
Inputs 1,2,3,4:
5 VDC @ 2 mA,intrinsically safe
Temperature inputs:
Vent(s) EPV-6000:
User Interface module:
menu driven set-up and operation
LED indication
Safe pressure:
Enclosure power:
Rapid exchange:
System bypass:
450 ft
(12.7 m
3
4 to 19
Gas, dust, or both
Manually ON and OFF
Automatically ON and OFF
20 to 30 VDC / 0.6 A
8 A @ 240 VAC,
resistive load
8 A @ 24 VDC
2 A @ 240 VAC,
resistive load
2 A @ 24 VDC
2 A @ 240 VAC,
resistive load
2 A @ 24 VDC
Contact input
6000-TEMP, intrinsically safe
Intrinsically safe connection via
connector
Up to 2 vents can be connected
Intrinsically safe connection via
M8 (V31) connector
2x20 LCD backlight screen for
BLUE – Safe pressure is
achieved
GREEN- power on
RED – power off
BLUE – when purging is
running
YELLOW – when bypass
is activated
Alarm fault:
)
3
I.S. solenoid valve output
Operating conditions
Indoor/outdoor use
Operating temp:
6000 control unit:
EPV-6000 vent:
Relative humidity:
Maximum altitude:
Pneumatic parameters
Protective gas requirement:
Pressure requirement:
Safe pressure minimum:
Gas:
Dust:
Gas+dust:
Purging flow rate increment and minimum enclosure
pressures at flow rate. Minimum purge time is 2 min:
EPV-6000-XX-01, 02
5 SCFM @ 1.5" wc, (141 l/min @ 3.7 mbar)
12 SCFM @ 2.0" wc, (340 l/min @ 5.0 mbar)
20 SCFM @ 2.7" wc, (565 l/min @ 6.7 mbar)
30 SCFM @ 4.1" wc, (850 l/min @ 10.2 mbar)
EPV-6000-XX-03, 04
5 SCFM @ 2.1" wc, (141 l/min @ 5.2 mbar)
12 SCFM @ 2.6" wc, (340 l/min @ 6.5 mbar)
20 SCFM @ 4.1" wc, (565 l/min @ 10.2 mbar)
30 SCFM @ 5.3" wc, (850 l/min @ 13.2 mbar)
EPV-6000-XX-05, 06
5 SCFM @ 1.5" wc, (141 l/min @ 4.5 mbar)
12 SCFM @ 2.9" wc, (340 l/min @ 7.3mbar)
Maximum flow rate measurement for enclosure size:
Enclosure volume
< 20 ft
3
(0.57 m
I/O Manual
RED blinking – any alarm
input detected
RED solid – 6000 series
system fault
Refer to drawing 116-013UL-112
This can be found on our website,
www.pepperl-fuchs.com
-20 °C to +60 °C (-4 °F to +140 °F)
-20 °C to +60 °C (-4 °F to +140 °F)
Up to 85 % non-condensing
2000 m
Instrument grade air
20 to 120 psig
(1.4 bar to 8.3 bar)
(138 kPa to 827 kPa)
(Filter + regulator not provided)
0.25" wc (6.4 mm wc)
(0.625 mbar) (62 Pa)
0.65" wc (16.5 mm wc)
(1.6 mbar) (162 Pa)
0.65" wc (16.5 mm wc)
(1.6 mbar) (162 Pa)
Flow rate
3
)
5, 12 SCFM
(141, 340 l/min)
or inert gas