6000 Series Purge/Pressurization System
Electrical & pneumatic diagrams
Complete 6000 full control unit power
connections (-WH-)
General wiring notes
For power connections to the 6000 control unit and
relay contacts:
1. All applicable local and national wiring codes
MUST be followed when wiring to the unit.
Warning
2. Ground wire to be 14 AWG (2.08 mm
length of ground to mate with pigtail under wire
Warning
nut .437" to .5" (11.1 mm to 12.7 mm).
3. If a single wire is used, the maximum wire gauge
to the pluggable terminal block is 14 AWG
(2.08 mm
).
2
4. If jumpering from one terminal to another at
pluggable terminal block, the maximum wire
gauge is 16 AWG (1.31 mm
5. Minimum wire gauge to the pluggable terminal
block is 24 AWG (0.20 mm
Attention
connector, not code. Follow all applicable
codes.)
6. Strip length of wires terminating into the screw
terminals on the pluggable terminal block to be
0.2" to 0.27" (5 mm to 7 mm).
7.
Add extra wire length of 1.25" (31.75 mm) past
top of opening in explosion-proof/flameproof box
to pluggable terminal block (allows connector
to be moved out of the way when changing
electronics. Prevents repouring seals).
8. Wires are to be neatly tucked back down past the
lid threads before lid is placed on unit. The wires
Warning
must not loop past the high point of the plastic
cover. The wire nut should be tucked in last (If
not, it may be difficult to access when changing
electronics).
9. If using a single conduit seal, the other conduit
on the 6000 control unit will need a cap for
Warning
the end of the conduit with appropriate hazloc
certifications (A standard 3/4" conduit cap will not
work).
10. Conduit seals with or without the 6000-CC-
3/4NPT plug must be within 18" (457.2 mm) of
Warning
internal explosion-proof/flameproof box, or within
15.25" (387.3 mm) from the end of the conduit
supplied with the 6000 unit.
11. When wiring to the terminal plug, it is easier
to remove the plug, terminate the wires, then
8
). Strip
2
) for both wires.
2
). (Based on
2
reconnect the plug.
12. When removing the pluggable terminal block, it
is recommended that the electronics module be
supported by pressing down on top of the EPCU
to counteract the lifting force required to remove
the connector.
13. Wire should be copper only, rated 90 °C
minimum. Minimum of 0.25" (6.3 mm) wire
Attention
insulation thickness required.
14. The minimum wire strand in a stranded wire
should have a diameter of 0.1 mm or greater.
15. The 6000-CC-3/4NPT plug is certified to be
used only with the 6000 control unit's ¾" nipples
Warning
coming out of the housing. This plug is not
certified to be used on any other hazardous
location equipment.
16. Ensure that electrical, mechanical, and
pneumatic connections and requirements are
met to operate this system. Please refer to
this manual and applicable standards/codes,
including current editio9n of the EN/IEC 60079-
14. Electrical supply to the purge system shall be
supplied through a switch or circuit breaker and
suitably located and easily reached and must be
marked as the disconnect for the equipment.
17. Power must be removed from the system when
the Ex d enclosure cover is off, unless the area is
Warning
known to be non-hazardous.
WARNING – To prevent ignition of the flammable
atmospheres, the wiring method must ensure that
Warning
if any wire is disconnected and extended to the
opposite terminal, a 2-inch separation must be
maintained.
I.S. wiring notes
For wires going to the explosion-proof/flameproof
box on the I.S. side:
1.
The wire strip length is to be between 0.2" and
0.27" (5 mm and 7 mm).
Attention
2. The wire's gauge depends on the number of
connections. Fewer wires allow for heavier
Attention
gauge and will still meet the conduit seal fill
requirement. See the applicable standards for fill
requirement.
3. The terminal blocks are rated for a wire size of
16 AWG (1.31 mm
I/O Manual
) to 28 AWG (0.08 mm
2
2
).