Speed Selection Dip Switches
Cool
Adjust
Selection
Selection
Switches
Switches
TAP
S1
S2
S3
A
OFF
OFF OFF OFF OFF OFF
B
ON
OFF ON
C
OFF
ON
OFF
D
ON
ON
ON
Profiles
Pre-Run
A
-------
B
-------
C
-------
D
30 sec/50%
To set Airflow: (1) Select model and desired High Stage Cooling
Airflow. Determine the corresponding tap (A, B, C, D). Set dip
switches S1 and S2 to the appropriate ON / OFF positions.
(2) Select model and installed electric heater size. Set dip
switches S9, S10, and S11 to the appropriate ON / OFF positions.
(3) If airflow adjustment is required set Trim Enable Switch
ON (OFF = 0% Trim) and set S3 and S4 to appropriate ON / OFF
positions. Tap A is +5%,Tap B is -5%, Tap C is +10%, Tap D is
-10%.
To Set Comfort mode: Select desired Comfort Mode Profile (see
profiles above). Set dip switches S5 and S6 to appropriate ON /
OFF positions.
Dehumidification: To enable, set dip switch S7 to ON. Cooling
airflow will be reduced to 85% of nominal value during cool call
when Dehum command is present. To disable, set S7 to OFF.
Continuous Fan Speed: Use dip switches S12 and S13 to select
one of 4 continuous fan speeds, Tap A is 25%. Tap B is 50%, Tap
C is 75%, Tap D is 100%.
Notes:
1. Airflow data shown applies to legacy mode operation only.
For a fully communicating system, please see the outdoor
unit's installation instructions for cooling and heat pump
airflow data. See ComfortNet System-Airflow Consideration
section for details.
2. Airflow blink codes are approximations of actual airflow.
HTR kW
9
10
11
AVPTC24B14A AVPTC30C14A AVPTC36C14A AVPTC48C14A AVPTC42D14A† AVPTC48D14A†† AVPTC60D14A†††
3
ON
ON
ON
5
ON
ON
OFF
6
ON
OFF
ON
8
ON
OFF
OFF
10
OFF
ON
ON
15
OFF
ON
OFF
19*
OFF
OFF
ON
20
21 or 25* OFF
OFF
OFF
Note: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operationNR - Not rated* Within thermostat
user menu, CTK0* communicating thermostat will display 20 kW for OFF-OFF-ON dip switch selection and
selection.
† For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
ON-ON-ON.
†† For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
††† For match up with a 3.5 ton outdoor unit: Heater kit application shall not exceed 20 kW.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor application.
Profile
Continuous
Selection
Fan
Switches
Speed
S4
S5
S6
S12
S13
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
Short-Run
OFF Delay
--------
60 sec/100%
30 sec/50%
60 sec/100%
7.5 min/82%
60 sec/100%
7.5 min/82%
30 sec/50%
S8
ELECTRIC HEAT AIRFLOW TABLE
550
600
650
700
700
750
800
875
850
950
NR
NR
NR
NR
NR
NR
NR
NR
Cooling/Heat Pump Airflow Table
Model
AVPTC24B14**
AVPTC30C14**
AVPTC36C14**
AVPTC48C14**
to
AVPTC42D14**
AVPTC48D14**
AVPTC60D14**
NOTE: Airflow blink codes are approximations of actual airflow. Airflows provided
are at 0.3 static.
NR
NR
850
850
900
900
1000
1000
1200
1200
1440
1440
1500
1500
1500
1500
NR
NR
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of
17
Low stage
Speed tap
(CFM)
A
410
565
B
C
660
765
D
A
440
B
605
C
740
885
D
A
500
B
700
930
C
1120
D
500
A
700
B
930
C
1120
D
560
A
B
765
C
995
1225
D
A
900
B
1035
1140
C
1200
D
A
1210
1365
B
1450
C
1525
D
850**
NR
1250
1250
1300
1300
1500
1500
1550
1550
1720
1720
NR
NR
1800
1815
NR
1850
21 kW for OFF-OFF-OFF dip switch
High stage
(CFM)
610
835
970
1125
610
835
1020
1225
725
1000
1330
1600
725
1000
1330
1600
800
1090
1420
1750
1350
1550
1700
1800
1610
1815
1920
2025
NR
1250
1300
1500
1550
1780
NR
1850
1850