Installation Instructions
A/GPD 14 SEER "M" SERIES - Single Package
Dual Fuel Gas-Electric Heating & Cooling Units
Affix this manual and Users Information Manual adjacent to the unit.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this
Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to
educate the customer on its safe use.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation of
single package gas electric heating and cooling units. See the
Specification Sheet applicable to your model* for information
regarding accessories.
*NOTE: Please contact your distributor or our website for the
applicable Specifications Sheets referred to in this manual.
This Forced Air Central Unit Design Complies With Requirements
Embodied in The American National Standard / National Standard
of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central Furnaces
*NOTE: Please contact your distributor or our website for the
applicable Specification Sheet referred to in this manual.
IO-407M
07/2021
Goodman Manufacturing Company, L.P.
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com or www.amana-hac.com
© 2011-2018, 2021 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Only personnel that have been trained to install, adjust, service
or repair(hereinafter, "service") the equipment specified in this
manual should service the equipment. The manufacturer will not
be responsible for any injury or property damage arising from
improper service or service procedures. If you service this unit,
you assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require one or
more licenses to service the equipment specified in this manual,
only licensed personnel should service the equipment.
Improper installation, adjustment, servicing or repair of the
equipment specified in this manual, or attempting to install,
adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property
damage, personal injury or death.
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the APD 14 M Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Goodman APD 14 M Series

  • Page 1 Goodman Manufacturing Company, L.P. 19001 Kermier Rd., Waller, TX 77484 www.goodmanmfg.com or www.amana-hac.com © 2011-2018, 2021 Goodman Manufacturing Company, L.P. IO-407M 07/2021 is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
  • Page 2 INDEX Condenser, Evaporator, and Induced Draft Motors .. 19 TO THE INSTALLER ............2 Flame Sensor (Qualified Servicer Only) ....19 TO THE OWNER .............. 2 Main Burner Flame (Qualified Servicer Only) .... 20 SHIPPING INSPECTION ..........2 APPENDIX ............... 21 SAFETY INSTRUCTIONS ..........
  • Page 3 FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
  • Page 4 AVERTISSEMENT RISQUE D'INTOXICATION AU MONOXYDE DE CARBON MONOXIDE POISONING HAZARD CARBONESi les étapes décrites ci-dessous ne sont pas Failure to follow the steps outlined below for each suivies pour chacun des appareils raccordés au système appliance connected to the venting system being de ventilation au moment de sa mise en marche, cela placed into operation could result in carbon monoxide peut entraîner une intoxication au monoxyde de...
  • Page 5: Ordering Parts

    American National Standards Institute 25 West 43rd street, 4th Floor HOMEOWNER SUPPORT New York, NY 10036 Goodman Manufacturing Company, L.P. PRE-INSTALLATION CHECKS 19001 KERMIER ROAD Before attempting any installation, the following points Houston, Texas 77484...
  • Page 6: All Installations

    All Installations: • The base should also be located where no runoff of water from higher ground can collect in the unit. • For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be • The top of the unit should be completely mounted level.
  • Page 7: Roof Curb Installations Only

    Roof Curb Installations Only: • Sufficient structural support must be determined prior to locating and mounting the curb and package unit. • Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. •...
  • Page 8 The gas/electric units naturally derate with altitude. Do exterior locations) not attempt to increase the firing rate by changing orifices • Listed gas appliance connectors used in or increasing the manifold pressure. This can cause poor accordance with the terms of their listing that are combustion and equipment failure.
  • Page 9: Propane Gas Installations

    5 to 15 PSIG First Stage (20 PSIG Max.) Regulator Continuous 11" W.C. 200 PSIG Second Stage Maximum Regulator Typical Propane Gas Piping Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting.
  • Page 10: High Voltage Wiring

    Propane Gas Sizing High Voltage Wiring Rated Voltage Minimum Supply Voltage Maximum Supply Voltage 208/230V The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram.
  • Page 11: Internal Wiring

    A diagram detailing the internal wiring of this unit is located Single phase models are shipped without horizontal duct on the Goodman labeled access panel. If any of the original covers. If needed, these kits may be ordered through wire supplied with the appliance must be replaced, the Goodman’s Service Parts department.
  • Page 12: Condensate Drain

    Filters Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. All units may be externally filtered. Refer to the unit filter size chart in the appendix for filter size information.
  • Page 13: Defrost Cycle

    enclosure. This enclosure will be mounted near the blower the thermostat is satisfied. access panel. The dimples and knock-out are located on the corner posts, providing ease of installation. Once 8. Gas valve(s) de-energizes. The induced draft blower the thermostat closes, a 24 volt signal is sent to the W1 continues operation for a 30-second post-purge.
  • Page 14: Air Flow Measurement And Adjustment

    and the reversing valve slides back to its normal heat with a 1-inch inclined manometer with pilot tubes or a position. Magnahelic gauge and confirm CFM to blower curves in the Specification Sheets. Cooling NOTE: Never run CFM below 350 CFM per ton, evaporator 1.
  • Page 15: Pre-Operation Checks

    Secondary Limit Control Open to Atmosphere The secondary limit control is located on the top of the High Fire Regulator blower scroll assembly. This control opens when elevated Outlet Adjust Regulator Pressure Boss Vent temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure.
  • Page 16 boss of the valve. Manifold Gas Pressure 5. Turn ON the gas supply. Range Nominal 6. Turn on power and energize main (M) solenoid. Do Natural Low Stage 1.6 -2.2” W.C. 2.0” W.C. not energize the HI solenoid. High Stage 3.2 - 3.8”...
  • Page 17 maximum allowable statics, check for closed dampers, dirty filters, undersizd or poorly laid out ductwork. Blower Speed Adjustments WARNING O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE BLOWER MOTOR.
  • Page 18: Cooling Start-Up

    3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or LO COOL recover charge to raise superheat. Superheat Formula = Suct. Line Temp. - Sat. Suct. HI COOL Temp. LO HEAT Return Air Temp. (°F Drybulb) Ambient HI HEAT Condenser Inlet...
  • Page 19: Maintenance

    5. The difference between the thermometer reading and Dirty filters are the most common cause of inadequate pressure to temperature conversion is the amount of heating or cooling performance. Filter inspection should be subcooling. made at least every two months; more often if necessary because of local conditions and usage.
  • Page 20: Main Burner Flame (Qualified Servicer Only)

    3. Remove the flue from the induced draft blower and 3. Remove the burners. the collector box cover from the partition panel. 4. Use a bottle brush to clean burner insert and inside 4. The primary heat exchanger tubes can be cleaned of the burners.
  • Page 21: Troubleshooting

    APPENDIX TROUBLESHOOTING DIAGNOSTIC CHECK CHECK STATUS LED - RED NORMAL OPERATION CHECK INPUT POWER NO POWER OR INTERNAL CONTROL CHECK FUSE(S) FAULT GAS FLOW GAS PRESSURE 1 FLASH IGNITION FAILURE GAS VALVE FLAME SENSOR CHECK PRESSURE SWITCH 2 FLASHES PRESSURE SWITCH OPEN CHECK TUBING CHECK VENT MOTOR PRESSURE SWITCH CLOSED...
  • Page 22: Ignition Control Diagnostic Indicator Chart

    IGNITION CONTROL DIAGNOSTIC INDICATOR CHART Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch Stuck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed...
  • Page 23: Unit Dimensions

    UNIT DIMENSIONS...
  • Page 24: Wiring Diagram

    WIRING DIAGRAM SEE NOTE 7 S R C SEE NOTE 8 COMP SEE NOTE 4 RCCF C-RV R-PS1 O-RV LVDR BL/PK BL/PK HVDR R-DFT P1 - PIN # 1 SEE NOTE 2 P1 - PIN # 6 P1 - PIN # 8 P1 - PIN # 3 P1 - PIN # 5 P1 - PIN # 2...
  • Page 25 WIRING DIAGRAM SUPPLY VOLTAGE 208-230/1/60 COMPONENT LEGEND SEE NOTE 7 AUXILLARY LIMIT SWITCH FACTORY WIRING CONTACTOR CRANKCASE HEATER LINE VOLTAGE SEE NOTE 8 CRANKCASE HEATER SWITCH LOW VOLTAGE CONDENSER MOTOR COMP OPTIONAL HIGH COMP COMPRESSOR RCCF C VOLTAGE DEFROST CONTROL BOARD DEFROST THERMOSTAT DEFROST RELAY FIELD WIRING...
  • Page 26: Minimum Clearances

    MINIMUM CLEARANCES Clearance in accordance with local installation codes, the requirements of the gas supplier and the manufacturer’s instal- lation instructions. Dégaugement conforme aux codes d’installation locaux, aux exigences du fournisseur de gaz et aux instructions d’instal- lation du fabricant NOTE: Roof overhang should be no more than 36".
  • Page 27: Blower Performance Data

    BLOWER PERFORMANCE DATA *PD1424060M41A* - Rise Range: 35° - 65° E.S.P Cooling Speed Cooling Speed Cooling Speed Stage Heating Speed Stage Heating Speed WATTS RISE WATTS RISE WATTS WATTS WATTS 1048 *PD1424070M41B* - Rise Range: 35° - 65° F E.S.P Cooling Speed Cooling Speed Cooling Speed...
  • Page 28 BLOWER PERFORMANCE DATA *PD1436080M41A* - Rise Range: 35° - 65° Cooling Speed Cooling Speed Cooling Speed Stage Heating Speed Stage Heating Speed E.S.P WATTS RISE WATTS RISE WATTS WATTS WATTS 1276 1317 1317 1453 1238 1269 1269 1405 1206 1221 1221 1357 1164...
  • Page 29 BLOWER PERFORMANCE DATA *PD1442115M41B* - Rise Range: 45° - 75° F E.S.P Cooling Speed Cooling Speed Cooling Speed Stage Heating Speed Stage Heating Speed WATTS RISE WATTS RISE WATTS WATTS WATTS 1090 1286 1354 1501 1609 1025 1225 1296 1446 1556 1165 1237...
  • Page 30: Start-Up Checklist

    Start-Up Checklist Residential Package - (Indoor Section) Model Number Serial Number ELECTRICAL Line Voltage (Measure L1 and L2 Voltage) L1 - L2 Secondary Voltage (Measure Transformer Output Voltage) R - C Blower Amps Heat Strip 1 - Amps Heat Strip 2 - Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure IN.
  • Page 31 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 32 Parts • Warranties • Contractor Programs and Training • Customer Service • Financing Options © 2011-2018, 2021 Goodman Manufacturing Company, L.P. is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.