DT9100 B
Wiring plan, connecting
the digital outputs
(see also "Application
example")
Be careful the polarity of
the cables.
20140130-V0
5.3. Connecting the digital outputs
A DT9100 B digital output is an output for direct driving an
other clock synchronising input or a NAMUR input.
You may connect an instrument to the output which input is
in comformity with the following output paremeters:
Uo < 10 V, Io < 200 mA, Po < 0,5 W.
The following figure shows the connection:
1. Push the cable-end until it possible into the terminal
assembly. By pushing the wire in, the self-closing
connection is being established.
2. Check it by pulling it outwards slightly.
19