Nailor BAC-8001-36 Installation And Operation Manual page 26

Ezvav series
Table of Contents

Advertisement

The airflow balancing procedure (continue)
PROCEDURE
4 Measure and enter the actual
minimum primary airflow.
5 Advance or exit.
6 Measure and enter the actual
maximum secondary airflow.
7 Measure and enter the actual
minimum secondary airflow.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
The display begins flashing PMIN and also displays
the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on the
lowest value for either the cooling or heating minimum
airflow even if only one mode is operational.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
button to advance to the entry display.
PMIN stops flashing.
4. Press the
or
airflow.
5. Press the
button to save the measured airflow.
The display advances to PRI.
1. Press the
or
following:
• SEC to balance the secondary VAV for dual duct
systems. Choosing SEC advances to the SMAX
display. This is available only on dual duct models.
• BACK to choose another commissioning function
• EXIT to return to the temperature display.
2. Press the
button to select the next function.
The display begins flashing SMAX and also displays
the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
button to advance to the entry display.
SMAX stops flashing.
4. Press the
or
airflow.
5. Press the
button to save the measured airflow.
The display advances to SMIN.
The display begins flashing SMIN and also displays
the actual airflow at the bottom.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
button to advance to the entry display.
SMIN stops flashing.
4. Press the
or
airflow.
5. Press the
button to save the measured airflow.
The display advances to SEC.
Page 26 of 48
EZvav Digital Controls
STEPS
buttons to enter the measured
buttons to select one of the
buttons to enter the measured
buttons to enter the measured
STE DISPLAY
PMIN
OO
PRI
SEC
SMAX
OO
SMIN
OO
IOM-EZVAVINST