Procedure to set the temperature set points (continue)
PROCEDURE
5 Set the occupied cooling set point.
6 Set the occupied heating set
point.
7 Set the unoccupied cooling set
point.
8 Set the unoccupied heating set
point.
9 Set the supply air temperature
changeover set point.
Not used in all models.
10 Set the minimum temperature
differential set point.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
This set point is used as the active set point when the
space is occupied.
1. Press the
or
cooling set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
Note: This set point can also be changed as described in
the topic Changing the room set point on page 13.
This set point is used as the active set point when the
space is occupied.
1. Press the
or
heating set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
Note: This set point can also be changed as described in
the section Changing the room set point on page 13.
This set point is used as the active set point when the
space is unoccupied.
1. Press the
or
cooling set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
This set point is used as the active set point when the
space is unoccupied.
1. Press the
or
heating set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
This set point sets the supply air temperature at which
the controller will change between heating to cooling.
1. Press the
or
point. The set point will change in 1° increments.
2. Press the
button to save the set point and
advance to the next function.
The minimum allowable temperature value between
the cooling and heating set points.
1. Press the
or
point. The set point will change in 1° increments.
2. Press the
button to save the set point and
advance to the next function.
Page 16 of 48
EZvav Digital Controls
STEPS
buttons to set the occupied
buttons to set the occupied
buttons to set the unoccupied
buttons to set the unoccupied
buttons to set the changeover set
buttons to set the differential set
STE DISPLAY
OCCL
74O
OCHT
7OO
UNCL
8OO
UNHT
62O
CHNG
74
DIFF
O5
IOM-EZVAVINST