Nailor BAC-8001-36 Installation And Operation Manual page 25

Ezvav series
Table of Contents

Advertisement

The airflow balancing procedure
PROCEDURE
1 Starting display.
2 Select the CNFG display.
3 Measure and enter the actual
maximum primary airflow.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
1. Start at the temperature display.
2. Press the
and
• If Password 2 is not required, the display changes to
CNFG.
• If required, enter Password 2. The display changes to
CNFG when Password 2 is correct.
1. From the CNFG display, press the
to advance to COMM and the BLNC display.
2. Press the
button to select BLNC. The display
advances to PRI.
3. Press the
button to select PRI.
The display begins flashing PMAX and also displays
the actual airflow at the bottom.
Note: The airflow will attempt to stabilize on the
highest value for either the cooling or heating
maximum airflow even if only one mode is operational.
Note: The airflow displayed by the STE-8000 in this
step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
button to advance to the entry display.
PMAX stops flashing.
4. Press the
or
airflow.
5. Press the
button to save the measured airflow.
The display changes to PMIN.
Page 25 of 48
EZvav Digital Controls
STEPS
buttons together.
or
buttons
buttons to enter the measured
STE DISPLAY

3
237
////
CNFG
COMM
BLNC
PRI
PMAX
OO
IOM-EZVAVINST

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bac-8005-36Tsp-8001-36Bac-8007-36

Table of Contents