Procedure to set the advanced options (continue)
PROCEDURE
2 Select the advanced display.
3 Change Password 1.
4 Change Password 2.
5 Set the standby time
Applies only to STE-8201 sensors.
6 Set the DAT Limiting mode.
Do not enable for staged
heating as short cycling
may occur.
7 Set the automatic occupancy
mode.
Not used for all models. Required
for reheat.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
1. From the CNFG display, press the
show the STPT display.
2. Press the
or
ADVC.
3. Press the
button to select ADVC.
Note: Entering four zeros (0000) removes the
password.
1. Press the
or
2. Press the
button to select the next digit. Repeat
for all four digits.
3. When the
button is pressed for the last digit, the
new password is saved and the display advances.
Note: Entering four zeros (0000) removes the
password.
1. Press the
or
2. Press the
button to select the next digit. Repeat
for all four digits.
3. When the
button is pressed for the last digit, the
new password is saved and the display advances.
1. Press the
or
standby time. The value will change in 1 minute
increments.
2. Press the
button to save the set point and
advance to the next function.
1. Press the
or
discharge air temperature limiting.
2. Press the
button to save the set point and
advance to the next function.
1. Press the
or
discharge air temperature limiting.
2. Press the
button to save the set point and
advance to the next function.
Enable The controller will automatically changed to the
unoccupied state when it detects the loss of primary
air supply.
Disable The controller will remain in the occupied
mode regardless of the primary air supply.
Page 22 of 48
EZvav Digital Controls
STEPS
buttons to
buttons to change the display to
buttons to change the first digit.
buttons to change the first digit.
buttons to set the time for the
buttons to enable or disable
buttons to enable or disable
STE DISPLAY
CNFG
STPT
ADVC
PSW1
OOOO
PSW2
OOOO
DAT
DISABLE
!5-$
$)3!",%
IOM-EZVAVINST