2.3.6

Resetting to factory defaults

In the event that the user name, password, or IP address of the Gateway is lost, the Gateway can be
restored to factory defaults by the procedure below.
Note
Following this procedure will cause the network to reform and all configuration parameters will be reset
to factory defaults. Once the Gateway is reset, the user is strongly recommended to change the default
password to maintain system security.
1. Turn off power to the Gateway, remove connectors, and un-mount the device from the DIN rail.
2. Locate the Reset switch label on the back of the Gateway.
3. Break the label in the center and slide the switch up.
4. Mount and reconnect the Gateway; turn power ON on to the gateway.
5. Let the Gateway completely boot up (approximately 2 minutes). During this time the red Reset light
on the front of the unit will be ON.
6. Turn off power to the Gateway, remove connectors and un-mount it from the rail again.
7. Return the Reset switch to lower position.
8. Mount and reconnect the Gateway; turn power ON on to the Gateway.
9. Verify the reset light is off, indicating the Reset switch is in the lower position. The Gateway will now
be programmed back to factory defaults including IP addresses. The factory default IP addresses can
be found in
Initial Connection
Table 2-1 on page
5.
Initial Connection
July 2017
11