Host Integration
July 2017
Figure 5-6. EtherNet/IP Communications Page
Table 5-3. System Settings>Protocols>Ethernet/IP
Terms
Assembly Object Type
EtherNet/IP TCP Port
EtherNet/IP UDP Ports
Incorporate value's associated status as error?
Value reported for error (floating point)
NaN
+Inf
-Inf
Other
Value reported for error (native integer)
36
Description
EtherNet/IP use Static assembly object.
The TCP Port used to access EtherNet/IP TCP data directly from the Gateway.
The UDP Ports used to access EtherNet/IP UDP data directly from the Gateway.
If the HART variable status indicates a critical failure or if there is a loss of
communications, it will be reported through the EtherNet/IP member.
Chooses what value is reported if the value's associated status indicates a critical
failure. Only used if the Gateway is using float representation
Not a number is reported if the value's associated status indicates a critical failure.
Positive infinity is reported if the value's associated status indicates a critical failure.
Negative infinity is reported if the value's associated status indicates a critical failure.
User defined value is reported if the value's associated status indicates a critical
failure.
User defined value is reported if the value's associated status indicates a critical
failure. Only used if the Gateway is using integer representation.
Reference Manual
00809-0200-4410, Rev BC
Host Integration