Table B–9: MODBUS MEMORY MAP (Sheet 30 of 43)
ADDR
REGISTER NAME
B0E0
IEC 61850 MMXU W.phsB Deadband 1
B0E2
IEC 61850 MMXU W.phsC Deadband 1
B0E4
IEC 61850 MMXU VAr.phsA Deadband 1
B0E6
IEC 61850 MMXU VAr.phsB Deadband 1
B0E8
IEC 61850 MMXU VAr.phsC Deadband 1
B0EA
IEC 61850 MMXU VA.phsA Deadband 1
B0EC
IEC 61850 MMXU VA.phsB Deadband 1
B0EE
IEC 61850 MMXU VA.phsC Deadband 1
B0F0
IEC 61850 MMXU PF.phsA Deadband 1
B0F2
IEC 61850 MMXU PF.phsB Deadband 1
B0F4
IEC 61850 MMXU PF.phsC Deadband 1
B0F6
...Repeated for Deadband 2
B12C
...Repeated for Deadband 3
B162
...Repeated for Deadband 4
B198
...Repeated for Deadband 5
B1CE
...Repeated for Deadband 6
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290
IEC 61850 configurable reports dataset items (64 items)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500
Number of Status Indications in GGIO1
B501
IEC 61850 GGIO1 Indication operands (128 items)
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function
B5A1
IEC 61850 Configurable GOOSE ID
B5C2
Configurable GOOSE Destination MAC Address
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
B5C6
IEC 61850 Configurable GOOSE VLAN ID
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
B5C8
IEC 61850 Configurable GOOSE ConfRev
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
B5CB
Configurable GOOSE dataset items for transmission
(64 items)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
B7B7
...Repeated for Module 6
B822
...Repeated for Module 7
B88D
...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules)
B900
Configurable GOOSE dataset items for reception
(32 items)
B940
...Repeated for Module 2
B980
...Repeated for Module 3
B9C0
...Repeated for Module 4
BA00
...Repeated for Module 5
BA40
...Repeated for Module 6
BA80
...Repeated for Module 7
BAC0
...Repeated for Module 8
Contact Inputs (Read/Write Setting) (96 modules)
BB00
Contact Input 1 Name
BB06
Contact Input 1 Events
BB07
Contact Input 1 Debounce Time
BB08
...Repeated for Contact Input 2
BB10
...Repeated for Contact Input 3
GE Multilin
RANGE
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0 to 848
8 to 128
---
0 to 1
---
---
0 to 7
0 to 4095
0 to 16383
1 to 4294967295
0 to 3
0 to 542
0 to 32
---
0 to 1
0 to 16
T35 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
---
1
F615
---
8
F001
---
1
F300
---
1
F102
---
---
F209
"GOOSEOut_x_"
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F611
---
1
F616
---
1
F233
---
---
F205
---
1
F102
ms
0.5
F001
DEFAULT
10000
10000
10000
10000
10000
B
10000
10000
10000
10000
10000
10000
0 (None)
8
0
0 (None)
0
4
0
0
1
3 (Relaxed)
0 (None)
0 (None)
"Cont Ip 1"
0 (Disabled)
20
B-37