GE T35 Instruction Manual page 235

Transformer protection system ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5 SETTINGS
Table 5–10: T35 FLEXLOGIC™ OPERANDS (Sheet 2 of 5)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT
LATCH 1 ON
Non-volatile latches
LATCH 1 OFF
LATCH 2 to LATCH 16
ELEMENT:
PHASE TOC1 PKP
Phase time
PHASE TOC1 OP
overcurrent
PHASE TOC1 DPO
PHASE TOC1 PKP A
PHASE TOC1 PKP B
PHASE TOC1 PKP C
PHASE TOC1 OP A
PHASE TOC1 OP B
PHASE TOC1 OP C
PHASE TOC1 DPO A
PHASE TOC1 DPO B
PHASE TOC1 DPO C
PHASE TOC2 to TOC6
ELEMENT:
SELECTOR 1 POS Y
Selector switch
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
ELEMENT:
SETTING GROUP ACT 1
Setting group
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
ELEMENT:
SH STAT GND STG1 PKP
Sub-harmonic stator
SH STAT GND STG1 DPO
ground fault detector
SH STAT GND STG1 OP
SH STAT GND STG2 PKP
SH STAT GND STG2 DPO
SH STAT GND STG2 OP
SH STAT GND OC PKP
SH STAT GND OC DPO
SH STAT GND OC OP
SH STAT GND TRB PKP
SH STAT GND TRB DPO
SH STAT GND TRB OP
ELEMENT:
SRC1 50DD OP
Disturbance
SRC2 50DD OP
detector
SRC3 50DD OP
SRC4 50DD OP
SRC5 50DD OP
SRC6 50DD OP
GE Multilin
OPERAND DESCRIPTION
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
At least one phase of phase time overcurrent 1 has picked up
At least one phase of phase time overcurrent 1 has operated
All phases of phase time overcurrent 1 have dropped out
Phase A of phase time overcurrent 1 has picked up
Phase B of phase time overcurrent 1 has picked up
Phase C of phase time overcurrent 1 has picked up
Phase A of phase time overcurrent 1 has operated
Phase B of phase time overcurrent 1 has operated
Phase C of phase time overcurrent 1 has operated
Phase A of phase time overcurrent 1 has dropped out
Phase B of phase time overcurrent 1 has dropped out
Phase C of phase time overcurrent 1 has dropped out
Same set of operands as shown for PHASE TOC1
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown above for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
---
---
---
---
---
---
---
---
---
---
---
---
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 5 disturbance detector has operated
Source 6 disturbance detector has operated
T35 Transformer Protection System
5.5 FLEXLOGIC™
5
5-101