Flex State Parameters - GE T35 Instruction Manual

Transformer protection system ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
From user-programmable
pushbuttons logic
sheet 1, 842021A3
5
Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2)
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
NOTE
EnerVista UR Setup with the Maintenance > Enable Pushbutton command.
PATH: SETTINGS
PRODUCT SETUP
 FLEX STATE
 PARAMETERS
5-54
LATCHED
LATCHED/SELF-RESET
PUSHBUTTON ON
SETTING
Message Priority
= Disabled
= High Priority
= Normal
Instantaneous reset will be executed if any
front panel button is pressed or any new
target or message becomes active.
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
PUSHBUTTON 3 ON
OR
PUSHBUTTON 16 ON
The enhanced front panel has 16 operands;
the standard front panel has 12


FLEX STATE PARAMETERS

PARAMETER
Off
PARAMETER
MESSAGE
Off
PARAMETER
MESSAGE
Off
PARAMETER 256:
MESSAGE
Off
T35 Transformer Protection System
SETTING
Flash Message Time
0
AND
OR
Instantaneous
reset *
AND
The message is temporarily removed if
any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores
the message.
AND
SETTING
Flash Message Time
0
AND
T
RST
Instantaneous
reset *
2. If pushbutton 1 LED control is not set to off.
FLEXLOGIC OPERAND
ANY PB ON
Range: FlexLogic™ operand
1:
Range: FlexLogic™ operand
2:
Range: FlexLogic™ operand
3:
Range: FlexLogic™ operand
5 SETTINGS
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
T
RST
On Text
= XXXXXXXXXX
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
OR
On Text
= XXXXXXXXXX
PUSHBUTTON 1 LED LOGIC
1. If pushbutton 1 LED control is set to off.
Pushbutton 1
FLEXLOGIC OPERAND
LED
PUSHBUTTON 1 ON
SETTING
Pushbutton 1
LED
PUSHBTN 1 LED CTL
= any FlexLogic operand
842024A2.CDR
5.2.14 FLEX STATE PARAMETERS