GE T35 Instruction Manual page 389

Transformer protection system ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 14 of 43)
ADDR
REGISTER NAME
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking Function
Transformer General (Read/Write Setting)
4630
Transformer Number Of Windings
4631
Transformer Phase Compensation
4632
Transformer Load Loss At Rated Load
4633
Transformer Rated Winding Temperature Rise
4634
Transformer No Load Loss
4635
Transformer Type Of Cooling
4636
Transformer Top-oil Rise Over Ambient
4637
Transformer Thermal Capacity
4638
Transformer Winding Thermal Time Constant
4639
Transformer Reference Winding Manual Selection
Transformer windings (read/write settings)
4640
Transformer Winding 1 Source
4641
Transformer Winding 1 Rated MVA
4643
Transformer Winding 1 Nominal Phase-Phase Voltage
4645
Transformer Winding 1 Connection
4646
Transformer Winding 1 Grounding
4647
Transformer Winding 1 Angle w.r.t. Winding 1
4651
Transformer Winding 1 Resistance
4653
...Repeated for Transformer Winding 2
4666
...Repeated for Transformer Winding 3
4679
...Repeated for Transformer Winding 4
468C
...Repeated for Transformer Winding 5
469F
...Repeated for Transformer Winding 6
Breaker control (read/write settings)
4700
Breaker 1 function
4701
Breaker 1 name
4704
Breaker 1 mode
4705
Breaker 1 open
4706
Breaker 1 close
4707
Breaker 1 phase A / three-pole closed
4708
Breaker 1 phase B closed
4709
Breaker 1 phase C closed
470A
Breaker 1 external alarm
470B
Breaker 1 alarm delay
470D
Breaker 1 pushbutton control
470E
Breaker 1 manual close recall time
4710
Breaker 1 out of service
4711
Breaker 1 block open
4712
Breaker 1 block close
4713
Breaker 1 phase A / three-pole opened
GE Multilin
RANGE
0 to 63
0 to 63
0 to 63
25 to 60
0 to 1
0 to 5
0 to 1
2 to 6
0 to 1
1 to 20000
0 to 4
1 to 20000
0 to 3
1 to 200
0 to 200
0.25 to 15
0 to 7
0 to 5
0.001 to 2000
0.001 to 2000
0 to 2
0 to 1
-359.9 to 0
0.0001 to 100
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
T35 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
---
1
F106
---
1
F167
---
1
F102
---
1
F001
---
1
F160
0 (Internal (software))
kW
1
F001
---
1
F161
kW
1
F001
---
1
F162
°C
1
F001
kWh/°C
0.01
F001
min
0.01
F001
---
1
F470
0 (Auto. Selection)
---
1
F167
MVA
0.001
F003
kV
0.001
F003
---
1
F163
---
1
F164
0 (Not within zone)
degrees
0.1
F002
ohms
0.0001
F003
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
DEFAULT
0
0
0
B
60
0 (ABC)
0 (SRC 1)
1 (Enabled)
2
100
1 (65°C (oil))
10
0 (OA)
35
10000
200
0 (SRC 1)
100000
220000
0 (Wye)
0
100000
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
B-21