The T35 Transformer Protection System has been designed to provide primary protection for medium to high voltage power
transformers. It performs this function on a variety of power transformer configurations with up to six sets of three phase
inputs available.
b) GENERAL TRANSFORMER SETTINGS

PATH: SETTINGS
SYSTEM SETUP
 GENERAL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1


TRANSFORMER

 GENERAL
 WINDING 1
 WINDING 2
 WINDING 3
 WINDING 4
 WINDING 5
 WINDING 6

TRANSFORMER
GENERAL
NUMBER OF WINDINGS:
2
REFERENCE WINDING:
Automatic Selection
PHASE COMPENSATION:
Internal (software)
LOAD LOSS AT RATED
LOAD:
100 kW
RATED WINDING TEMP
RISE: 65°C (oil)
NO LOAD LOSS:
10 kW
TYPE OF COOLING:
OA
T35 Transformer Protection System
5.4 SYSTEM SETUP
5.4.4 TRANSFORMER
See page 5–73.
See page 5–75.
See page 5–75.
See page 5–75.
See page 5–75.
See page 5–75.
See page 5–75.
Range: 2 to 6 in steps of 1
Range: Automatic Selection, Winding 1, Winding 2,...,
Winding 6
Range: Internal (software), External (with CTs)
Range: 1 to 20000 kW in steps of 1
Range: 55°C (oil), 65°C (oil), 80°C (dry), 115°C (dry),
150°C (dry)
Range: 1 to 20000 kW in steps of 1
Range: OA, FA, Non-directed FOA/FOW, Directed FOA/
FOW