GE T35 Instruction Manual page 234

Transformer protection system ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5.5 FLEXLOGIC™
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–10: T35 FLEXLOGIC™ OPERANDS (Sheet 1 of 5)
OPERAND TYPE
OPERAND SYNTAX
CONTROL
CONTROL PUSHBTN 1 ON
PUSHBUTTONS
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIRECT INPUT/
DIR IO CH1 CRC ALARM
OUTPUT
CHANNEL
DIR IO CH2 CRC ALARM
MONITORING
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
ELEMENT:
BKR ARC 1 OP
Breaker arcing
BKR ARC 2 OP
ELEMENT:
BREAKER 1 OFF CMD
Breaker control
BREAKER 1 ON CMD
BREAKER 1 A BAD ST
5
BREAKER 1 A INTERM
BREAKER 1 A CLSD
BREAKER 1 A OPEN
BREAKER 1 B BAD ST
BREAKER 1 A INTERM
BREAKER 1 B CLSD
BREAKER 1 B OPEN
BREAKER 1 C BAD ST
BREAKER 1 A INTERM
BREAKER 1 C CLSD
BREAKER 1 C OPEN
BREAKER 1 BAD STATUS
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
BREAKER 2...
ELEMENT:
Counter 1 HI
Digital counters
Counter 1 EQL
Counter 1 LO
Counter 2 to Counter 8
ELEMENT:
FxE 1 PKP
FlexElements™
FxE 1 OP
FxE 1 DPO
FxE 2 to FxE 16
ELEMENT:
GROUND TOC1 PKP
Ground time
GROUND TOC1 OP
overcurrent
GROUND TOC1 DPO
GROUND TOC2
5-100
OPERAND DESCRIPTION
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level.
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level.
The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
Breaker arcing current 1 has operated
Breaker arcing current 2 has operated
Breaker 1 open command initiated
Breaker 1 close command initiated
Breaker 1 phase A bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase A is closed
Breaker 1 phase A is open
Breaker 1 phase B bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase B is closed
Breaker 1 phase B is open
Breaker 1 phase C bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase C is closed
Breaker 1 phase C is open
Breaker 1 bad status is detected on any pole
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
Same set of operands as shown for BREAKER 1
Digital counter 1 output is 'more than' comparison value
Digital counter 1 output is 'equal to' comparison value
Digital counter 1 output is 'less than' comparison value
Same set of operands as shown for Counter 1
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
Same set of operands as shown for FxE 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
T35 Transformer Protection System
5 SETTINGS
GE Multilin

Advertisement