Testable Safety Device - Reer MOSAIC Master M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC Master M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
The TESTABLE SAFETY DEVICE functional block
checks the status of the Inx inputs of a single or
double safety sensor, both NO and NC. Refer to the
tables below to check type of sensor and behaviour.
(single NC)
0
0
1
1
(double NC)
0
0
0
1
1
0
1
1
* Simultaneity error = the maximum time between switching of the single contacts
has been exceeded.
Parameters
Manual Reset: If selected, enables the reset request after each activation of the device.
Otherwise, enabling of the output follows directly the conditions of the inputs. Reset may
be of two types: Manual and Monitored. Selecting the Manual option, only transition of
the signal from 0 to 1 is checked. If Monitored is selected, double transition from 0 to 1
and return to 0 is checked.
WARNING: if Reset is enabled, the input consecutive to those used by the functional
block must be used. For example: If inputs 1 and 2 are used for the functional
block, input 3 must be used for Reset.
95
(single NO)
0
1
Simultaneity error *
X
X
t = 250ms
0
1
0
0
0
1
1
0
1
1
t1 > 250ms
t2 = 250ms
(double NC-NO)
Simultaneity error *
X
-
-
X
8540780 • 30/03/2016 • Rev.26