MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
The MONOSTABILE operator generates a level 1 (TRUE)
output activated by the rising edge of the input and
remains in this condition for the set time.
Parameters
Time: The delay can be set to between 10 ms and
1098.3 s.
Rising edge: If selected, the output is set to 1 (TRUE) on the input signal's rising edge
where it remains for the set time, which can be extended for as long as the input stays at
1 (TRUE).
In
T
Out
If not selected the logic is inverted, the output is set to 0 (FALSE) on the input signal's
falling edge, where it remains for the set time, which can be extended for as long as the
input stays at 0 (FALSE).
In
T
Out
Retriggerable: If selected the time is reset each time the input status changes.
8540780 • 30/03/2016 • Rev.26
T
T
T
T
Rising edge
Falling edge
119