C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
Header.
Substation.
Communication.
IED section (one or more).
DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
C
Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The Substation node describes the substation parameters:
C-18
SCL
Header (id, version, revision, toolID, nameStructure)
Substation
Communication
IED Section (IED 1)
IED Section (IED 2)
Other IED Sections
DataTypeTemplates
Figure 0–6: SCD FILE STRUCTURE, SCL (ROOT) NODE
Substation
EquipmentContainer
VoltageLevel
Function
842792A1.CDR
Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE
B30 Bus Differential System
842791A1.CDR
PowerSystemResource
Power Transformer
GeneralEquipment
EquipmentContainer
Bay
Voltage
PowerSystemResource
SubFunction
GeneralEquipment
APPENDIX C