2.2 SPECIFICATIONS

2.2SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
2
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
power system devices via communications or different output contacts. In addition, operate times are given here for
a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
BUS DIFFERENTIAL (87B)
Pickup level:
Low slope:
High slope:
Low breakpoint:
High breakpoint:
High set level:
Dropout level:
Level accuracy:
0.1 to 2.0  CT rating: ±0.5% of reading or ±1% of rated (which-
>2.0  CT rating
Operating time:
Number of zones:
CT TROUBLE
Responding to:
Pickup level:
Pickup delay:
PHASE/NEUTRAL/GROUND TOC
Current:
Pickup level:
Dropout level:
Level accuracy:
for 0.1 to 2.0  CT:
for > 2.0  CT:
Curve shapes:
Curve multiplier:
Reset type:
Curve timing accuracy
at 1.03 to 20 x pickup:
2-10
0.050 to 6.000 pu in steps of 0.001
15 to 100% in steps of 1
50 to 100% in steps of 1
1.00 to 30.00 pu in steps of 0.01
1.00 to 30.00 pu in steps of 0.01
0.10 to 99.99 pu in steps of 0.01
97 to 98% of pickup
ever is greater)
±1.5% of reading
one power system cycle (typical)
2
Differential current
0.020 to 2.000 pu in steps of 0.001
1.0 to 60.0 sec. in steps of 0.1
Phasor or RMS
0.000 to 30.000 pu in steps of 0.001
97% to 98% of pickup
±0.5% of reading or ±0.4% of rated
(whichever is greater)
±1.5% of reading > 2.0  CT rating
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
2
Extremely Inverse; I
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Time Dial = 0.00 to 600.00 in steps of
0.01
Instantaneous/Timed (per IEEE)
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
B30 Bus Differential System
2 PRODUCT DESCRIPTION

2.2.1 PROTECTION ELEMENTS

PHASE/NEUTRAL/GROUND IOC
Current:
Phasor only
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0  CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0  CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
<16 ms at 3  pickup at 60 Hz
Operate time:
(Phase/Ground IOC)
<20 ms at 3  pickup at 60 Hz
(Neutral IOC)
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
PHASE UNDERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Curve shapes:
GE IAV Inverse;
Definite Time (0.1s base curve)
Curve multiplier:
Time dial = 0.00 to 600.00 in steps of
0.01
Curve timing accuracy
at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle
(whichever is greater) from pickup to
operate
NEUTRAL OVERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 s in steps of 0.01 (definite
time) or user-defined curve
Reset delay:
0.00 to 600.00 s in steps of 0.01
Curve timing accuracy
at >1.1 x pickup:
±3.5% of operate time or ±1 cycle
(whichever is greater) from pickup to
operate
30 ms at 1.10  pickup at 60 Hz
Operate time: