GE B30 Instruction Manual page 170

Multilin b30 bus differential system ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The relay supports one fast Ethernet Global Data (EGD) exchange and two slow EGD exchanges. There are 20 data items
in the fast-produced EGD exchange and 50 data items in each slow-produced exchange.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to 'produce' EGD data exchanges, and other devices can be configured to 'consume' EGD
data exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
EGD cannot be used to transfer data between UR-series relays. The relay supports EGD production only. An EGD
exchange will not be transmitted unless the destination address is non-zero, and at least the first data item address is set to
a valid Modbus register address. Note that the default setting value of "0" is considered invalid.
The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS
PRODUCT SETUP
 FAST PROD EXCH 1
 CONFIGURATION
5
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The B30 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the slow EGD exchanges is shown below:
PATH: SETTINGS
PRODUCT SETUP
 SLOW PROD EXCH 1
 CONFIGURATION
5-46

COMMUNICATIONS
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
MESSAGE
0.0.0.0
EXCH 1 DATA RATE:
MESSAGE
1000 ms
EXCH 1 DATA ITEM 1:
MESSAGE
0
EXCH 1 DATA ITEM 2:
MESSAGE
0
EXCH 1 DATA ITEM 3:
MESSAGE
0
EXCH 1 DATA ITEM 20:
MESSAGE
0

COMMUNICATIONS
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
MESSAGE
0.0.0.0
EXCH 1 DATA RATE:
MESSAGE
1000 ms
EXCH 1 DATA ITEM
MESSAGE
0
EXCH 1 DATA ITEM
MESSAGE
0
EXCH 1 DATA ITEM
MESSAGE
0
EXCH 1 DATA ITEM 50:
MESSAGE
0
B30 Bus Differential System

EGD PROTOCOL
FAST PROD EXCH 1 CONFIGURATION
Range: Disable, Enable
Range: standard IP address
Range: 50 to 1000 ms in steps of 1
Range: 0 to 65535 in steps of 1
(Modbus register address range)
Range: 0 to 65535 in steps of 1
(Modbus register address range)
Range: 0 to 65535 in steps of 1
(Modbus register address range)
Range: 0 to 65535 in steps of 1
(Modbus register address range)

EGD PROTOCOL
SLOW PROD EXCH 1(2) CONFIGURATION
Range: Disable, Enable
Range: standard IP address
Range: 500 to 1000 ms in steps of 1
Range: 0 to 65535 in steps of 1
1:
(Modbus register address range in decimal)
Range: 0 to 65535 in steps of 1
2:
(Modbus register address range in decimal)
Range: 0 to 65535 in steps of 1
3:
(Modbus register address range in decimal)
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents