GE B30 Instruction Manual page 259

Multilin b30 bus differential system ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5 SETTINGS
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE
SETTING
GROUND TOC1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
GROUND TOC1
SOURCE:
IG
SETTING
GROUND TOC1
BLOCK:
Off = 0
b) GROUND INSTANTANEOUS OVERCURRENT (ANSI 50G, IEC PIOC)

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND IOC1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
GE Multilin
SETTINGS
GROUND TOC1
INPUT:
GROUND TOC1
PICKUP:
GROUND TOC1
CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1
RESET:
AND
RUN
IG ≥ PICKUP
t
I
Figure 5–55: GROUND TOC1 SCHEME LOGIC

SETTING GROUP 1(6)
GROUND IOC1
FUNCTION: Disabled
GROUND IOC1 SIGNAL
SOURCE: SRC 1
GROUND IOC1
PICKUP:
1.000 pu
GROUND IOC1 PICKUP
DELAY:
0.00 s
GROUND IOC1 RESET
DELAY:
0.00 s
GROUND IOC1 BLOCK:
Off
GROUND IOC1
TARGET: Self-reset
GROUND IOC1
EVENTS: Disabled
B30 Bus Differential System
5.6 GROUPED ELEMENTS
FLEXLOGIC OPERANDS
GROUND TOC1 PKP
GROUND TOC1 DPO
GROUND TOC1 OP
827036A3.VSD

GROUND CURRENT
GROUND IOC1(6)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-reset, Latched
Range: Disabled, Enabled
5
,
Disabled
5-135

Advertisement

Table of Contents
loading

Table of Contents