7.2 TARGETS
c) MINOR SELF-TEST ERROR MESSAGES
Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in the
Settings chapter for additional details.
IEC 61850 DATA SET:
LLN0 GOOSE# Error
Latched target message: No.
Description of problem: A data item in a configurable GOOSE data set is not supported by the B30 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the GOOSE data set are supported by the B30. The EnerVista UR Setup soft-
ware will list the valid items. An IEC61850 client will also show which nodes are available for the B30.
IEC 61850 DATA SET:
LLN0 BR# Error
Latched target message: No.
Description of problem: A data item in a configurable report data set is not supported by the B30 order code.
How often the test is performed: On power up
What to do: Verify that all the items in the configurable report data set are supported by the B30. The EnerVista UR
Setup software will list the valid items. An IEC61850 client will also show which nodes are available for the B30.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is not functioning.
How often the test is performed: The battery is monitored every five seconds. The error message displays after 60 sec-
onds if the problem persists
What to do: Return the power supply module to GE Digital Energy for battery replacement. To instead dispose of the
battery and power supply module, see the battery disposal information at the beginning of this manual.
7
MAINTENANCE ALERT:
Direct I/O Ring Break
Latched target message: No.
Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
How often the test is performed: Every second
What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
Latched target message: No.
Description of problem: A bad IRIG-B input signal has been detected.
How often the test is performed: Monitored whenever an IRIG-B signal is received.
What to do: Ensure the following:
The IRIG-B cable is properly connected.
Proper cable functionality (that is, check for physical damage or perform a continuity test).
7-6
.
.
.
.
B30 Bus Differential System
7 COMMANDS AND TARGETS