Communicator Reset; Establishing A Communication Channel With The Scw9055/Scw9057 Panel - DSC 3G2075 Installation Manual

Hspa/3g wireless alarm communicator ethernet/internet and hspa/3g dual-path alarm communicator
Table of Contents

Advertisement

3G Alarm Communicator Installation Manual
6. When inserting a SIM card, insert the card in the proper orientation and gently push the SIM card holder down and slide the holder
as indicated by the arrow on SIM holder, to LOCK.
7. Apply AC power to panel, and replace the panel cover.
NOTE: If two way audio is enabled you will NOT be able to swap the SIM card with another card.
C
R
OMMUNICATOR
ESET
The Communicator can be reset by cycling the power on the SCW9055/SCW9057.
E
C
STABLISHING A
OMMUNICATION
The Communicator interfaces to the SCW9055/SCW9057 through a keyed 16 pin Ribbon cable. See Table 5 . The key prevents incor-
rect connection of the ribbon cable connector to the SCW9055/SCW9057 and Communicator. The pinout for the Ribbon cable is pro-
vided in the Table below:
Table 5: Communicator Ribbon cable to SCW9055/SCW9057
Pin #
Signal
1
PC-Link TX
3
GND
5
Vref
7
AUD-OUT_N
9
AUD-IN_P
11
GND
13
GND
15
GND
Establishing a communication channel between the Communicator and the SCW9055/SCW9057 is critical to ensuring the desired
operation of the two units. The following steps must be completed during the on-site installation. Program the following to ensure that
the Communicator and the panel will work together as intended.
Initial Programming of Communicator and SCW9055/SCW9057
1. Enter [*][8][Installer Code] [Section Number] for panel programming. Record any values that are modified from their default, in the
appropriate Programming Worksheets.
NOTE: When programming Toggle Options, the toggle is ON when the number is displayed and OFF when the number is not dis-
played. (e.g., [1 - - - 5 - - - ], Toggle Options 1 and 5 are ON, all others are OFF).
2. Panel Section [167] Cellular/Ethernet Interface Communications 'Wait for ACK': Default value is: 060 seconds.
3. When the communicator is installed with the SCW9055/SCW9057 panel, 4 telephone numbers are available to backup one another.
You can set up these 4 telephone numbers to perform in one of two ways: Backup dialling or Alternate dialling.
a. Backup dialling: each of the 4 telephone numbers will make 5 dialling attempts in turn, before an FTC trouble is displayed on
the keypad.
b. Alternate dialling: each telephone number makes 1 dialling attempt before moving on to the next number, cycling through each
of the 4 numbers for a total of 5 times each. If all 4 numbers fail the 5 attempts, an FTC trouble is displayed on the keypad.
4. Panel Sections [301], [302], [303], and [305] can be configured as Primary communication paths.
a. Panel Sections [302], [303], and [305] may also be configured for backup or redundant communications by using Panel Sec-
tion(s) [383] or [351] - [376]. Refer to the SCW9055/SCW9057 panel Installation Manual for more information.
b. If a valid telephone number is programmed, communications will use Public Switched Telephone Network (PSTN). Entering a 4
digit hexadecimal value for a telephone number will change the call routing to the Communicator, as determined by the number
programmed:
DCAAF:
Internal (All Receivers). Signals will be routed depending on Section [851] [006] programming.
DCBBF:
Ethernet Receiver 1 (Primary). (Not available for 3G2075).
DCCCF:
Ethernet Receiver 2 (Backup). (Not available for 3G2075).
NOTE: Add a single 'F' as a suffix to the 4 digit hex number to populate the unused remainder of the 32 character field.
5. Panel Section [350]: If any of the phone numbers have been programmed as DCAA, DCBB, DCCC, DCDD, or DCEE, panel Sec-
tion [350] must be set to [04] if SIA format or [03] if Contact ID (CID) format is used by control panel.
6. Panel Section [382]: Toggle Option [5], 'GS/IP Module Enabled', must be set to ON.
7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel DLS session through Cellular or Ethernet data
channel.
8. Panel section [310], account code, auto syncs with the communicator account code in section [021]. The panel account code
([*][8][installer code] [310]), will overwrite the communicator account code section ([*][8][installer code] [850] [021]) if pro-
grammed differently.
NOTE: Keep a record of the SIM card telephone number, it is required by users for SMS Command and Control functions. (The num-
ber can be recorded in the Programming Worksheets Section of this document, under Option [996]). Due to the nature of the
SIM card activation process with Cellular network carriers, it can take up to 24 hours for SIM card activation to be complete.
C
HANNEL WITH THE
Pin #
Signal
2
PC-Link RX
4
Vref
6
GND
8
AUD-OUT_P
10
AUD-IN_N
12
SI
14
SO
16
Wall Tamper
SCW9055/SCW9057 P