Drive Parameter Listing - YASKAWA CIMR-V7xx20P1 series Installation Manual

V7 series; v74x series
Table of Contents

Advertisement

Drive Parameter Listing

(n001-n004)
The Drive control circuits use various parameters to select functions and characteristics of the Drive. Changing of parameter
settings must be done in the Program mode, or by use of the Function LEDs, if available (see TM.V7.01, Section 4).
The following table lists all parameters in numerical order. For each parameter, reference paragraph(s) in TM.V7.01, Section 5
are listed (if applicable) where the features of the Drive affected by that parameter are described.
PARA-
METER
n001
n002
n003
n004
36
NAME
0: n001 can be read and set;
n002 - n179 read only
1: n001 - n039 can be read and set
2: n001 - n079 can be read and set
3: n001 - n119 can be read and set
Parameter Selection /
4: n001 - n179 can be read and set
Initialization
5: n001 - n179 can be read and set
Run command accepted during Program
6: Clear Fault History Only
7: Not Used
8: 2-wire Initialization (Japan Spec.)
9: 3-wire Initialization (Japan Spec.)
10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)
0: V/f Control
Control Method Selection
1: Open Loop Vector
0: Digital Operator
Operation Method Selection
1: Terminal
2: Serial Communication (Modbus)
3: Option Card
0: Digital Operator Pot
1: Digital Operator
2: Voltage Reference (0 to 10V)
3: Current Reference (4 to 20 mA)
4: Current Reference (0 to 20 mA)
Reference Selection
5: Pulse Train Reference
6: Serial Communications (Modbus)
7: Multi-Function Analog Input (0 to 10V)
8: Multi-Function Analog Input (4 to 20 mA)
9: Option Card
V7 Parameters
SETTING RANGE
(AND UNITS)
INCREMENT
mode
SETTING
FACTORY
USER
SETTING
SETTING
1
1
1
0
1
1
1
2
Section 8
PARA.
REF.
5.21
2.2
5.13
5.11,
5.13

Advertisement

Table of Contents
loading