6.2 STATUS
The
AVERAGE MSG RETURN TIME
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The
UNRETURNED MSG COUNT
make the trip around the communications ring. The
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The
values can be cleared using the
COUNT
The
to
DIRECT INPUT 1
PATH: ACTUAL VALUES
 DIRECT DEVICES
 STATUS
These actual values represent the state of direct devices 1 through 16.
PATH: ACTUAL VALUES
 IEC 61850
6
 GOOSE UINTEGERS
The F60 Feeder Protection System is provided with optional IEC 61850 communications capability. This
feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2
for additional details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
a) FAST EXCHANGE
PATH: ACTUAL VALUES
 FAST EXCHANGE 1
6-10
is the time taken for direct output messages to return to the sender in a direct input/output
values (one per communications channel) count the direct output messages that do not
CLEAR DIRECT I/O COUNTERS
values represent the state of each direct input.
DIRECT INPUT (32)

STATUS

DIRECT DEVICES STATUS

DIRECT DEVICE 1
STATUS: Offline
DIRECT DEVICE 2
MESSAGE
STATUS: Offline
DIRECT DEVICE 16
MESSAGE
STATUS: Offline


STATUS
IEC 61850 GOOSE UINTEGERS
UINT INPUT
UINT INPUT
MESSAGE
UINT INPUT 16
MESSAGE

STATUS
EGD PROTOCOL STATUS
FAST EXCHANGE 1
SIGNATURE:
FAST EXCHANGE 1
MESSAGE
DATA LENGTH:
F60 Feeder Protection System
values (one per communications channel) count the
CRC FAIL COUNT
command.
Range: Offline, Online
Range: Offline, Online
Range: Offline, Online
1
0
2
0
0
PRODUCER STATUS
0
0
6 ACTUAL VALUES
and
UNRETURNED MSG COUNT
6.2.17 DIRECT DEVICES STATUS
6.2.18 IEC 61850 GOOSE INTEGERS
6.2.19 EGD PROTOCOL STATUS
FAST EXCHANGE 1
CRC FAIL
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents