GE F60 Instruction Manual page 147

Ur series feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

5 SETTINGS
Table 5–2: ACCESS RIGHTS SUMMARY
FIELD
DESCRIPTION
Event Recorder
Allows the user to use the digital fault recorder
FlexLogic
Allows the user to read FlexLogic values
Update Info
Allows the user to write to any function to which they have read privileges. When any of the Settings, Event
Recorder, and FlexLogic check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the Update Info box, they are granted read and write access.
The user is not granted write access to functions that are not checked, even if the Update Info field is
checked.
Admin
The user is an EnerVista UR Setup administrator, therefore receiving all of the administrative rights.
Exercise caution when granting administrator rights.
4.
Click OK to save the changes.
f) CYBERSENTRY SECURITY
The EnerVista software provides the means to configure and authenticate UR using either device or server authentication.
The access to various pieces of functionality depends on user role.
The login screen of EnerVista has two options for access to the UR, server and device authentication.
When the "Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authen-
ticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login
accounts and the associated passwords are stored on the UR device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server authenti-
cation (RADIUS) only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.