B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 68)
ADDR
REGISTER NAME
6475
Overfrequency 1 Pickup Delay
6476
Overfrequency 1 Reset Delay
6477
Overfrequency 1 Target
6478
Overfrequency 1 Events
6479
Reserved (4 items)
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
6680
Sensitive Directional Power 1 Function
B
6681
Sensitive Directional Power 1 Signal Source
6682
Sensitive Directional Power 1 RCA
6683
Sensitive Directional Power 1 Calibration
6684
Sensitive Directional Power 1 STG1 SMIN
6685
Sensitive Directional Power 1 STG1 Delay
6686
Sensitive Directional Power 1 STG2 SMIN
6687
Sensitive Directional Power 1 STG2 Delay
6688
Sensitive Directional Power 1 Block
668A
Sensitive Directional Power 1 Target
668B
Sensitive Directional Power 1 Events
668C
Reserved (5 items)
6691
...Repeated for Sensitive Directional Power 2
Load Encroachment (Read/Write Grouped Setting)
66C0
Load Encroachment Function
66C1
Load Encroachment Source
66C2
Load Encroachment Minimum Voltage
66C3
Load Encroachment Reach
66C4
Load Encroachment Angle
66C5
Load Encroachment Pickup Delay
66C6
Load Encroachment Reset Delay
66C7
Load Encroachment Block
66C9
Load Encroachment Target
66CA
Load Encroachment Events
66CB
Reserved (6 items)
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7008
Phase Undervoltage 1 Target
7009
Phase Undervoltage 1 Events
700A
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
7015
...Repeated for Phase Undervoltage 2
7017
...Repeated for Phase Undervoltage 2
701B
...Repeated for Phase Undervoltage 2
701C
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
7025
...Repeated for Phase Undervoltage 3
B-40
RANGE
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 359
0 to 0.95
-1.2 to 1.2
0 to 600
-1.2 to 1.2
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0.02 to 250
5 to 50
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
F60 Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
degrees
1
F001
degrees
0.05
F001
pu
0.001
F002
s
0.01
F001
pu
0.001
F002
s
0.01
F001
---
---
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
0 (Definite Time)
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
---
1
F001
DEFAULT
500
500
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0
0
100
50
100
2000
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
250
100
30
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Phase to
Ground)
0
GE Multilin