5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) HIGH IMPEDANCE FAULT DETECTION
PATH: SETTINGS
CONTROL ELEMENTS
HI-Z
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
MONITORING ELEMENTS
HI-Z
BREAKER 1
ARCING CURRENT
BREAKER 2
ARCING CURRENT
BREAKER
FLASHOVER 1
BREAKER
FLASHOVER 2
BREAKER RESTRIKE 1
INCIPIENT FAULT 1
INCIPIENT FAULT 2
VT FUSE FAILURE 1
VT FUSE FAILURE 2
BROKEN CONDUCTOR 1
BROKEN CONDUCTOR 2
THERMAL OVERLOAD
PROTECTION
MONITORING ELEMENTS
HI-Z FUNCTION:
Disabled
HI-Z SOURCE:
SRC 1
HI-Z ARCING
SENSITIVITY:
5
HI-Z ARCING DET SOE
RESET TIME: 0.0 s
HI-Z PHASE EVENT
COUNT:
30
HI-Z GROUND EVENT
COUNT:
30
F60 Feeder Protection System
5.7 CONTROL ELEMENTS
5.7.12 MONITORING ELEMENTS
See page 5–239.
See page 5–245.
See page 5–245.
See page 5–247.
See page 5–247.
See page 5–251.
See page 5–253.
See page 5–253.
See page 5–255.
See page 5–255.
See page 5–257.
See page 5–257.
See page 5–258.
HI-Z
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 1 to 10 in steps of 1
Range: 0.0 to 6000.0 s in steps of 0.1
Range: 10 to 250 in steps of 1
Range: 10 to 500 in steps of 1
5
5-239