IBM zEnterprise EC12 Installation Manual page 58

For physical planning 2827 all models gc28-6914-01 level 01f
Table of Contents

Advertisement

Level 01f
The following table and chart illustrate how to determine the amount of chilled air your computer room
must provide to meet the environmental requirement for your zEC12.
Table 10. Cooling airflow graph codes - H20
Cooling
Model
method
H20 typical
Radiator-cooled
H20 maximum
Radiator-cooled
H20 typical
Water-cooled
H20 maximum
Water-cooled
Table 11. Cooling airflow graph codes - H43
Cooling
Model
method
H43 typical
Radiator-cooled
H43 maximum
Radiator-cooled
H43 typical
Water-cooled
H43 maximum
Water-cooled
Table 12. Cooling airflow graph codes - H66
Cooling
Model
method
H66 typical
Radiator-cooled
H66 maximum
Radiator-cooled
H66 typical
Water-cooled
H66 maximum
Water-cooled
Table 13. Cooling airflow graph codes - H89
Cooling
Model
method
H89 typical
Radiator-cooled
H89 maximum
Radiator-cooled
H89 typical
Water-cooled
H89 maximum
Water-cooled
Table 14. Cooling airflow graph codes - HA1
Cooling
Model
method
HA1 typical
Radiator-cooled
HA1 maximum
Radiator-cooled
HA1 typical
Water-cooled
HA1 maximum
Water-cooled
44
zEC12 IMPP
Total power
Power to water
(in kw)
(in kw)
5.4
13.4
5.1
3.8
13.1
9.8
Total power
Power to water
(in kw)
(in kw)
10.0
19.8
9.4
7.0
19.1
14.3
Total power
Power to water
(in kw)
(in kw)
14.2
23.3
13.3
10.0
22.5
16.9
Total power
Power to water
(in kw)
(in kw)
19.4
26.9
18.4
13.8
25.9
19.5
Total power
Power to water
(in kw)
(in kw)
19.4
27.6
18.4
13.8
26.6
20.0
Power to air
(in kw)
-
5.4
-
13.4
1.3
3.3
Power to air
(in kw)
-
10.0
-
19.8
2.4
4.8
Power to air
(in kw)
-
14.2
-
23.3
3.3
5.6
Power to air
(in kw)
-
19.4
-
26.9
4.6
6.4
Power to air
(in kw)
-
19.4
-
27.6
4.6
6.6
Use cooling
curve
B
D
A
A
Use cooling
curve
D
G
A
B
Use cooling
curve
F
H
A
B
Use cooling
curve
H
I
B
C
Use cooling
curve
H
I
B
C