Level 01f
The following figure and tables show sample floor loading values for the zEC12, with and without the
Internal Battery Feature (3213), and without the top exit I/O feature (7942).
Floor loading for radiator-cooled servers without Internal Battery Feature
Example #
'a' (sides) mm (in)
1
25 (1.0)
2
25 (1.0)
3
25 (1.0)
4
254 (10.0)
5
254 (10.0)
6
254 (10.0)
7
508 (20.0)
8
508 (20.0)
9
508 (20.0)
10
762 (30.0)
11
762 (30.0)
12
762 (30.0)
Floor loading for radiator-cooled servers with Internal Battery Feature
Example #
'a' (sides) mm (in)
1
25 (1.0)
2
25 (1.0)
3
25 (1.0)
4
254 (10.0)
5
254 (10.0)
6
254 (10.0)
7
508 (20.0)
8
508 (20.0)
34
zEC12 IMPP
'b' (front) mm (in)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
'b' (front) mm (in)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
'c' (rear) mm (in)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
Floor load kg/m
'c' (rear) mm (in)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
762 (30.0)
254 (10.0)
508 (20.0)
2
Floor load kg/m
2
(lbs/ft
)
892.69 (182.84)
722.32 (147.94)
613.83 (125.72)
723.16 (148.12)
590.41 (120.93)
505.88 (103.61)
605.48 (124.01)
498.84 (102.17)
430.94 (88.26)
526.48 (107.83)
437.38 (89.58)
380.65 (77.96)
2
2
(lbs/ft
)
979.21 (200.56)
789.63 (161.73)
668.92 (137.01)
790.57 (161.92)
642.86 (131.67)
548.81 (112.40)
659.62 (135.10)
540.97 (110.80)