v The side cover of either an A or Z frame cannot be placed adjacent to a wall (Example A), but can be
positioned next to obstacles such as poles or columns (Example B).
v The front cover on frame A and both covers on frame Z open 329.1 mm (13.0 in) wider than the width
of the frame plus side cover (Example C).
v Service clearances cannot be achieved with a zEC12 server installed side-cover-to-side-cover.
Dimensions are given for zEC12 next to a zEC12. To calculate side-to-side clearance, add 329.1 mm
(13.0 in) to the clearance required from the adjacent equipment (Example D).
Wall or
other obstacle
Example A
329.1 mm (13.0 in)
frame Z to wall
OK
OK
OK
Figure 9. Detailed service clearances
OK
Example B
OK
OK
Wall
OK
Example C
OK
OK
OK
Example D
468 mm
(18.4 in)
OK
OK
Column
Pole
329.1 mm (13.0 in)
frame A to wall
Chapter 3. Models and physical specifications