Level 01f
Meets the ASHRAE recommended guidelines
Meets the ASHRAE allowable guidelines
Exceeds the ASHRAE environmental limits
Data center temperature in degrees Celsius (C)
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
Figure 4. Environmental specifications - bar graph format
It is very important the environmental specifications be met immediately in front of both frames of
the zEC12. Ideally, it would be best if the temperature and humidity controls are good enough to
surround the service area of the zEC12. If you are able to exceed the required conditions, focus your
efforts to provide the best quality air at the bottom front of the server.
14
zEC12 IMPP
0
0
15 C minimum, 32 C maximum