The service rating for all 200–240 V ac plug types is as follows:
v Maximum voltage: 250 V ac
v Current: see Table 47
v Phases: 1
v Wires: 3
Table 47. Specifications for 200–240 V ac power cord used with the IBM System Storage TS3500 Tape Library,
Models L32 and D32
Length and Type of
Power Cord
4.3 m (14 ft)
non-watertight twistlock
(default in the U.S.,
Canada, Japan, Korea,
Philippines, and Taiwan)
4.3 m (14 ft) (in countries
or regions other than the
U.S., Canada, Japan,
Korea, Philippines, and
Taiwan)
4.3 m (14 ft) watertight
(in the U.S., Canada,
Japan, Korea, Philippines,
and Taiwan)
1.8 m (6 ft) watertight (in
Chicago, Illinois, U.S.)
Single Branch Circuit 30 A Service Rating
Part Number
Type of Service
and Feature
Receptacle
Code
NEMA L6-30R
11F0113 / 9987
(receptacle 3)
46F6063 / None
Per local requirements
Russellstoll connectors
3933 or 9C33U0 or
46F4594 / 9988
receptacles 3753 or
9R33U0W (receptacle 5)
Russellstoll connectors
3933 or 9C33U0 or
46F4593 / 9986
receptacles 3753 or
9R33U0W (receptacle 5)
Dual AC Line Cords 15 A Service Rating
(Feature Code 1901)
Part Number
Type of Service
and Feature
Code
NEMA L6-15R
14F1550 / 9987
(receptacle 2)
IEC 309 Type 2P+GND,
16 A for example,
36L8823 / None
Hubbell HBL316R6W
(receptacle 6)
Russellstoll connectors
3913U2 or 9C23U2 or
86F2646 / 9988
receptacles 3743U2 or
9R23U2W (receptacle 4)
Russellstoll connectors
3913U2 or 9C23U2 or
86F2645 / 9986
receptacles 3743U2 or
9R23U2 (receptacle 4)
Chapter 2. Physical planning specifications
Receptacle
125