total. In order to calculate the total cooling required by the library (in Btu/hr),
multiply the total power in watts by 3.4. To convert Btu/hr to kBtu/hr, divide
your result by 1000.
Table 45 provides a sample calculation of total power and cooling requirements for
a TS3500 Tape Library configuration consisting of one L23 with ten TS1130 tape
drives and mounting kits, four D23 models each containing six TS1130 tape drives
and mounting kits, one D23 with no drives or enhanced FCA feature (FC 1451),
two S24 models, and one HA1 model.
Table 45. Sample calculation of total library power consumption and cooling requirements.
With this
This model
feature
code
L23
1
1515
D23
(with FC
1515
2
1451
)
D23
(without
N/A
FC 1451)
S24
N/A
HA1
N/A
Total power consumption:
Total cooling requirement (kBtu/hr):
Notes:
1. FC 1515: Tape drive mounting kit for L23 and D23 frames.
2. FC 1451: Enhanced frame control assembly for D23 and D53 frames.
Library power consumption is dynamic and usage dependent. Short peaks might
exceed the maximum continuous power values. Typical average power
consumption is lower than the calculated maximum continuous value because all
drives are not likely to be active simultaneously.
And these
Quantity
tape drives
1
10
TS1130
10
4
24
TS1130
24
N/A
1
N/A
2
N/A
1
Power (Watts)
Off
Idle
continuous
13
142
0
40
0
170
52
412
0
96
0
408
0
0
0
10
0
24
65
1302
0.2
4.4
Max.
202
70
460
412
168
1104
0
10
85
2511
8.5