10 Supplement
Max. emitted HF power of the antenna system
Ʋ Pulse peak power
Ʋ Pulse duration
Ʋ Average power
Ʋ Average power with 1 m distance
Max. emitted HF power of the antenna system - Version with increased sensitivity
Ʋ Pulse peak power
Ʋ Pulse duration
Ʋ Average power
Ʋ Average power with 1 m distance
Measuring accuracy
Resolution, general
Deviation
7)
10 mm (0.394 in)
3 mm (0.116 in)
0
- 3 mm (- 0.116 in)
- 10 mm (- 0.394 in)
Fig. 34: Deviation VEGAPULS 63
30 mm (1.180 in)
15 mm (0.590 in)
0
- 15 mm (- 0.590 in)
- 30 mm (- 1.180 in)
Fig. 35: Deviation VEGAPULS 63 with increased sensitivity in mm, measuring range in m
Influence of the ambient temperature to the sensor electronics
Average temperature coefficient of the
zero signal (temperature error)
Incl. non-linearity, hysteresis and non-repeatability.
7)
Relating to the nominal measuring range, in the temperature range -40 ... +80 °C .
8)
52
< 2 mW
< 2 ns
< 5 µW
< 200 nW/cm
< 10 mW
< 2 ns
< 25 µW
< 1 µW/cm
max. 1 mm (0.039 in)
see diagrams
0,5 m (1.6 ft)
1,0 m (3.280 ft)
0.03 %/10 K
2
2
8)
VEGAPULS 63 • Foundation Fieldbus
20 m (65.62 ft)
20 m (65.62 ft)