6 Set up with the display and adjustment module PLICSCOM
Basic adjustment - Sen-
sor TAG
Display - Indicated value
Display - Backlight
34
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Caution:
Note the following if the VEGAPULS 63 with corresponding approval
is used as part of an overfill protection system according to WHG
(Water Resources Act):
If a linearisation curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when setting the switching point on the limit signal
transmitter.
In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product des-
ignation. In digital systems and in the documentation of larger plants,
a singular designation should be entered for exact identification of
individual measuring points.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and you can
now jump to the main menu with the [ESC] key.
Menu section, display
Radar, guided microwave and ultrasonic sensors deliver the following
measured values:
SV1 (Secondary Value 1): Percentage value after the adjustment
SV2 (Secondary Value 2): Distance value before the adjustment
PV (Primary Value): Linearised percentage value
AI FB1 (Out)
In the menu item "Display" you can define which value should be
indicated on the display.
Displayed value
AI-Out
A background lighting integrated by default can be adjusted via the
adjustment menu. The function depends on the height of the supply
voltage. See "Technical data/Voltage supply".
Backlight
In the default setting, the lightning is switched off.
VEGAPULS 63 • Foundation Fieldbus