Profibus pa concentration density transmitter (102 pages)
Summary of Contents for SMAR LD400
Page 1
OPERATION AND MAINTENANCE INSTRUCTION / MANUAL Smart Pressure Transmitter LD400 L D 4 0 0 M E...
Page 2
Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp...
Page 3
This instruments can be configured through Smar configuration softwares or others supplier. The local adjustment is enable for all the LD400 series. With magnetic tools is possible to configure the zero and the span, to alter the measurement range, to alter the unit of measured pressure, to select the square root function, to operate the totaled value or in a control loop.
Page 4
Smar provides specific training to instruct and qualify such professionals. However, each country must comply with the local safety procedures,...
Page 5
The process variable, as well as the diagnostic monitoring and information, are supplied by the ® digital communication protocol. The LD400 is available in the HART communication protocol. ® Read carefully these instructions for better use of the LD400 HART . Smar pressure transmitters are protected by American patents n. 6,433,791 and 6,621,443.
Page 6
LD400 - Operation and Maintenance Instruction Manual Acronyms and Abbreviations Acronym / Designation Description Abbreviation Hardware Fault Tolerance The hardware fault tolerance of the device. This is the capability of a functional unit to continue the execution of the demanded function in case of faults or deviations.
Page 8
LD400 - Operation and Maintenance Instruction Manual INTERCHANGEABILITY ............................6.8 RETURNING MATERIALS ............................6.8 LIFETIME TRANSMITTER ............................6.8 ACESSORIES ................................6.9 SPARE PARTS LIST ..............................6.9 ORDERING CODE ..............................6.11 ® HART SPECIAL UNITS ............................6.16 SECTION 7 - SAFETY INSTRUMENTED SYSTEMS ................7.1 INTRODUCTION ................................
Page 9
Installation Flowchart Installation Flowchart Start Was the transmitter Install the transmitter on the field configured on the bench following the instructions below. to match the application? Install the transmitter preferably on weather- protected areas. Configure the transmitter (Section 1 and 3) Check the area classification and its practices Configure the measuring range...
Page 10
LD400 - Operation and Maintenance Instruction Manual VIII...
There are, however, ways of reducing the effects of temperature, humidity and vibration. ® The LD400 HART has a built-in temperature sensor to compensate for temperature variations. At the factory, each transmitter is submitted to a temperature cycle, and the characteristics under different temperatures are recorded in the transmitter memory.
Page 12
(blow-down). Shu the valves tightly after each drain or discharge operation. ® Figure 1.1 (a) – Dimensional Drawing and Mounting Position for the LD400 HART – Differential Pressure, Flow, Gage, Absolute and High Static Pressure Transmitter with Mounting Bracket...
Page 13
Installation ® Figure 1.1 (b) – Dimensional Drawing and Mounting Position for the LD400 HART – Flanged Pressure Transmitter (Integral Flange)
Page 14
® LD400 HART – Operation and Maintenance Instruction Manual ® Figure 1.1 (c) – Dimensional Drawing and Mounting Position for the LD400 HART – Flanged Pressure Transmitter (Slip-on Flange)
Page 15
Installation ® Figure 1.1 (d) – Dimensional Drawing and Mounting Position for the LD400 HART – Flanged Pressure Transmitter with Housing...
Page 16
® LD400 HART – Operation and Maintenance Instruction Manual ® Figure 1.1 (d) – Dimensional Drawing and Mounting Position for the LD400 HART – Sanitary Transmitter with Extension...
Page 17
Installation ® Figure 1.1 (e) – Dimensional Drawing and Mounting Position for the LD400 HART – Sanitary Transmitter without Extension...
Page 18
MOUNTING ON THE PANEL OR WALL (See Section 6 –spare parts for mounting brackets available) ® Figure 1.2 – Drawing of LD400 HART Mounted on the Panel or Wall Some examples of installation, illustrating the transmitter position in relation to the taps, are shown in Figure 1.3.
Page 19
Installation ® For fiscal measuring and custody transference, use a safety seal on the LD400 HART , as shown below. Figure 1.4 – Safety Seal and Custody Transference When the sensor is in the horizontal position, the fluid weight pushes the diaphragm down and then the lower pressure trim must be applied.
® LD400 HART – Operation and Maintenance Instruction Manual Electronic Housing The electronic housing can be rotated to adjust the digital display on a better position. To rotate it, loose the Housing Rotation Set Screw, see Figure 1.6. COVER LOCKING...
Page 21
TEST COMUNICATIONS TERMINALS TERMINALS GROUND TERMINAL ® Figura 1.8 – LD400 HART Terminal Block NOTE The external ground was designed to accept wiring up to 10 mm² section (S=12 mm²). Use a heavy duty conductor, at least Ø 1,6mm²/15 AWG.
The ungrounded end must be carefully isolated. On multidrop connections, the circuit loop integrity must be assured, with special care to prevent short-circuit between the circuit loop and the housing. ® Figure 1.10 – Wiring Diagram for the LD400 HART Working as a Transmitter 1.12...
Page 23
Installation ® Figure 1.11 – Wiring Diagram for the LD400 HART Working as a Controller ® Figure 1.12 – Wiring Diagram for the LD400 HART in Multidrop Configuration NOTE Make sure that the transmitter is operating within the operating area as shown on the load curve (Figure 1.13).
In Explosion-Proof installations the cable entries must be connected or closed using metal cable gland and metal blanking plug, both with at least IP66 and Ex-d certification. The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug needs to be replaced, a certified plug must be used.
Section 2 FUNCTIONAL DESCRIPTION Functional Description – Sensor ® The LD400 HART Smart Pressure Transmitters use capacitive sensors (capacitive cells) as pressure sensing elements, as shown in Figure 2.1 Figure 2.1 – Capacitive Cell Where: and P are the pressures in chambers H and L.
ELECTRONIC CONVERTER DIGITAL DISPLAY ® Figure 2.2 – LD400 HART Block Diagram Hardware Oscillator This oscillator generates a frequency as a function of sensor capacitance. Signal Isolator The Control signals from the CPU are transferred through optical couplers, and the signal from the oscillator is transferred through a transformer.
Page 27
3.6 mA; during operation, consumption may be as high as 21 ® mA, depending on the measurement and sensor status. The LD400 HART in the transmitter mode shows failure indication at 3.6 mA if configured for low signal failure; at 21 mA, if configured for high signal failure;...
LD400 HART – Operation and Maintenance Instruction Manual ® Functional Description – LD400 HART Software Refer to the block diagram Figure 2.3. The function of each block is described below. Factory Characterization The actual pressure from the capacitance and temperature readouts obtained from the sensor can be calculated by using the factory characterization data stored in the sensor EEPROM.
Page 29
Functional Description Block PID: Bumpless A/M On the Manual mode, the PID algoritm uses the output values as a compensation to its proportional action so that the Manual to Automatic transition do not occur abruptly . Therefore, even if the transition occurs in the presence of a percent ERROR., the proportional action is nullified and the output is adjusted softly according to the integral action.
INDICATES THAT UNIT AND FUNCTION FIELD THE SETPOINT VARIABLE IS NOW DISPLAYED IS NOW DISPLAYED ® Figure 2.4 – Display for LD400 HART ® Figure 2.5 – Display for LD400 HART Monitoring ® During normal operation, the LD400 HART is in the monitoring mode. In this mode, indication alternates between the three variables (LCD_1, LCD_2, LCD_3) as configured by the user.
Page 32
Table 2.1. For a complete list, see Section 6 – Maintenance. INDICATOR DESCRIPTION Numeric Alphanumeric ® Version LD400 HART and Version The LD400 HART is initialized after feeding. Output current saturated on 3.8 or 20.5 mA. (see section 5 – Variable Value SAT / Unit Maintenance)
Certifications Explosion proof, intrinsically safe and dust ignition proof (FM) (Pending) Authorized representative in European Community Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach ATEX Directive 94/9/EC - “Electrical equipment and protective system intended for use in potential explosive atmospheres” The EC-Type Examination Certificate had been released by Nemko AS (CE0470) and/or DEKRA EXAM GmbH (CE0158), according to European Standards.
Page 34
Configuration ® In order to keep the equipment configuration safe, the LD400 HART has two kinds of write protection in its memory. One is via software and the other a hardware mechanism selected by a key with priority over the software.
Page 35
Technical Characteristics Functional Specifications PRESSURES TABLE FOR SEAL AND LEVEL FLANGES DIN EN 1092-1 2008 STANDARD Maximum Temperature Allowed Material Pressure Group Class Maximum Pressure Allowed (bar) PN 16 13.7 12.3 11.2 10.4 PN 25 21.5 19.2 17.5 16.3 15.1 14.4 PN 40 34.4...
Page 36
® – Operation and Maintenance Instruction Manual LD400 HART Functional Specifications Maximum Temperature Allowed Material Pressure -29 to Group Class Maximum Pressure Allowed (bar) 15.9 15.3 13.3 11.2 10.5 41.4 34.8 31.4 29.2 27.5 26.1 25.5 25.1 Overpressure and 55.2 53.4...
Page 38
Plated Carbon Steel, 316 SST-CF8M (ASTM - A351), Hastelloy C276 - CW-12MW, (ASTM - A494) or Monel 400 O-Rings (For Flanges and Adapters): Buna-N, Viton™ PTFE or Ethylene-Propylene. The LD400 HART is available in NACE MR-01-75/ISO 15156 compliant materials. Electronic Housing: Injected aluminum with polyester painting, epoxy painting or 316 SST - CF8M (ASTM - A351) housing.
Page 39
Technical Characteristics Identification Plate: 316 SST a) Flange mounted for Level models. b) Optional universal mounting bracket for surface or vertical/horizontal 2"- pipe (DN 50). Mounting c) Manifold Valve integrated to the transmitter. d) Directly on piping for closely coupled transmitter/orifice flange combinations. 3.15 kg (7 lb): all models, except L models.
® – Operation and Maintenance Instruction Manual LD400 HART Ordering Code MODEL DIFERENTIAL PRESSURE, FLOW, GAGE, ABSOLUTE AND HIGH STATIC PRESSURE TRANSMITTER LD400 Smart Pressure Transmitter Turn Down RANGE LIMITS Type Min. Max. Unid. Min. Max. Unid. Max. Diferential (23)
Page 41
Technical Characteristics LD400-D210-H0-IBD11 DIFERENTIAL PRESSURE, FLOW, GAGE, ABSOLUTE AND HIGH STATIC PRESSURE TRANSMITTER (CONTINUATION) Flanges Bolts and Nuts Material Plated Carbon Steel (Default) (20) 316 SST Carbon Steel (ASTM A193 B7M) (1) (20) Hastelloy C276 Super Duplex Stainless Steel Nace MR0175 / MR0103 Compliant...
Page 42
® – Operation and Maintenance Instruction Manual LD400 HART MODEL FLANGED PRESSURE TRANSMITTER LD400 Smart Pressure Transmitter RANGE LIMIT Turn Down TYPE Unidd Min Max Unit Level -500 mbar The range can be extended up to 0.75 LRL and 1.2 URL with small...
Page 44
(13) Only available for ANSI B16.5 flange. Product CEPEL NEMKO / EXAM (14) Don´t available for JIS 2202 flange. LD400 IP66/68W IP66/68W Type4X/6P (15) For this option consult Smar. (16) Don´t available for aluminium housing. (28) Not available for integral flange. 3.12...
Page 45
Technical Characteristics MODEL SANITARY PRESSURE TRANSMITTER LD400 Smart Pressure Transmitter RANGE LIMIT Turn Down TYPE Unid. Max Unid. Sanitary -500 mbar Note: The range can be extended up to 0.75 LRL and 1.2 URL with Sanitary -250 -2500 2500 mbar small degradation of accuracy.
Page 46
® – Operation and Maintenance Instruction Manual LD400 HART LD400-S210-H0-HBDU0-P0 SANITARY PRESSURE TRANSMITTER (CONTINUATION) COD. Process Connection (High Side) DN25 DIN 11851 – WITH EXTENSION/316 SST DN40 DIN 11851 - WITH EXTENSION/316 SST DN40 DIN 11851 – 316 SST THREAD DN50 DIN 11851 - WITH EXTENSION/316 SST...
Page 47
NEMKO (ATEX) COD TAG Plate With TAG, when specified Blanket According to user notes COD HART Configuration LD400-S210-H0-HBDU0-P04-B10-I110I - TYPICAL MODEL NUMBER ® ** Fill out with HART Optional Configuration (see page 3.14) Notes: Meets NACE MR – 01 – 75/ISO 15156 recommendations.
Page 48
TABLE - The output is a curve formed by 16 points. These points may be edited directly on the XY Table of the LD400. For example, it may be used as a camber table for tanks in applications where the tank volume is not linear in relation to the measured pressure.
Command Specification – LD400 Intelligent Pressure Transmitter. Smar developed the CONF401 and HPC401 software (See figure 4.2), the first one works in Windows platform (95, 98, 2000, XP and NT) and UNIX. The second one, HPC401, works in the most recent technology in PDA. (See figure 4.1). They provide easy configuration and monitoring of field devices, capability to analyze data and to modify the action of these devices.
Page 50
® Operation and Maintenance Instruction Manual LD400 HART – Figure 4.1 – Smar Hand Held Terminal Figure 4.2 – Smar Configuration Tool Figure 3.3 show the menu tree used for configuration based on version 4.02 DD.
Page 51
Configuration DESCRIPTOR MESSAGE DATE SENSOR MODEL SENSOR TYPE SENSOR RANGE NOMINAL RANGE SENSOR SERIAL # FILL FLUID DIAPHRAGM MAT. NUM of REM.SEAL SENSOR INFO TYPE MATERIAL FLANGE INFORMATION O'RING DRAIN/VENT TYPE REMOTE SEAL FILL FLUID DIAPHRAGM MANUFACTURER DEVICE TYPE DEVICE ID NUMBER MAIN BOARD SERIAL SOFTWARE VERSION DEVICE INFO...
® Operation and Maintenance Instruction Manual LD400 HART – Configuration Features ® By means of the HART configuration tool, the LD400 HART firmware allows the following configuration features to be accessed: Transmitter Identification and Manufacturing Data; Primary Variable Trim – Pressure;...
4 mA output. If the signal is 100%, the output should be 20 There might be differences between the Smar current standards and your current plant Standard. In this case, the Current Trim adjustment shall be done with a precision ammeter as measurement reference.
® For pressure measurements, the LD400 HART includes an option list with the most common units. The internal reference unit is inH O @ 20 ºC; should the desired unit be other than this one, it will be automatically converted using conversion factors included in Table 4.1.
Page 56
Should a special unit other than those presented on Table 4.2 be required, the LD400 HART ® allows the user to create a new unit by entering up to 5 alphanumeric digits. The LD400 HART includes an internal feature to enable and disable the User Unit.
This gives a more stable reading at low flows. ® In order to find the square root, the LD400 HART configurable parameters are: cutoff point defined at a certain pressure expressed as % and the cutoff mode, hard or bumpless.
For example, in tank maneuvering there are several pipes where the ® direction of the fluid may vary. In this case, LD400 HART has the bidirectional flow measurement function. This function treats the flow, no matter what its direction is, as if it were positive. Thus, it is possible to extract the square root and measure the bidirectional flow.
Page 59
Configuration The method uses such totalization and, through three parameters (MAXIMUM FLOWRATE, TOTAL INCREMENT and TOTAL UNIT), converts it to the user-defined totalizing unit: MAXIMUM FLOW RATE - this is the maximum flow rate expressed in volume or mass units per second, corresponding to the measurement (PV%=100%).
For a better linearization, it is recommendable that the points are the closest ® possible, in the less linear regions of the curve. The LD400 HART has an internal variable to enable and disable the characterization table of the MV output of the PID.
The output current will be increased to 4 mA as the LD400 HART address, in the Transmitter ® mode, is altered to another value than "0" (this does not happen when the LD400 HART configured in the Controller mode). ®...
Circuit Number - This number is unique to each main circuit board and cannot be changed. ® Sensor Number - The serial number of the sensor connected to the LD400 HART and cannot be changed. This number is read from the sensor every time a new sensor is inserted in the main board.
Page 63
Configuration VARIABLE DESCRIPTION Lower Value/Upper Value When any type of calibration is done. When any change in the transference function is done, e.g., linear, Function square root, const, table. Trim_4mA When the current trim is done at 4mA. Trim_20mA When the current trim is done at 20mA. Trim_Zero/Lower When pressure trim is done at Zero or Lower Pressure.
PROGRAMMING USING LOCAL ADJUSTMENT The Magnetic Tool ® With the Magnetic Tool it is possible to configure locally the LD400 HART and eliminate the need for additional configurators in many basic applications. ® There are two ways to adjust the LD400 HART locally according to the jumper configuration (see Table 5.1):...
Page 66
® LD400 HART – Operation and Maintenance Instruction Manual Local Adjustment Simple Mode Enable Disable Complete Mode Enable Writing Protection Enable Writing Disable Writing Table 5.1– Local Adjustment Selection Notes: 1 - If the writing protection (WP ON) is selected, the writing in EEPROM will be protected.
The transmitter software automatically starts to display the available functions in a cyclic routine. The group of functions ® displayed depends on the mode selected for the LD400 HART , either Transmitter or Controller.
® LD400 HART – Operation and Maintenance Instruction Manual NOTE For adequate calibration, notice the minimum span for each measuring range and types as defined on the Technical Specification (Section 3). Zero calibration with reference shall be done as follows: Apply the Lower Value pressure;...
Page 69
Programming Using Local Adjustment DISPLAY SIMUL RANGE TRIM CONF OPER QUIT 4 mA Zero Reference PSWRD Damp Reset Total Quit PASSWORD Span Reference 8 mA DAMP Trim 12 mA DAMP Lower 16 mA Save Lower 20 mA Lower ESC SIMUL Save Function Save...
® LD400 HART – Operation and Maintenance Instruction Manual WARNING When programming using local adjustment, the transmitter will not prompt "Control loop should be in ® manual!" as it does when using the HART configurator for programming. Therefore it is a good idea, before configuration, to switch the loop to manual.
S: Escapes to the Simulation Branch [SIMUL]. SIMUL NOTE ® After entering a simulation current value, the LD400 HART automatically quits the simulation mode in around 2 minutes. Other configuration branches are also abandoned in fairly less time, around 8 seconds. Range [RANGE] This option makes zero and span calibration, also called calibration with reference, or define lower and upper operation values, while performing calibration without reference.
Page 72
® LD400 HART – Operation and Maintenance Instruction Manual RANGE TRIM ZERO SPAN UNIT RANGE inH2O inHg ftH2O Save Save mmH2O mmHg mBar gf/cm2 kgf/cm2 mH2O Figure 5.5 – Range Calibration Branch of Complete Local Adjustment Tree RANGE BRANCH [RANGE] Z: Moves enter main branch options of complete local adjustment tree.
Page 73
Programming Using Local Adjustment Z: Moves enter LRV DECREASE function. S: Increases the Lower Value until the magnetic tool is removed or the maximum Lower Value is reached. Z: Moves enter options Lower Range Value Adjustment Branch. [LRV]. S: Decreases the Lower Value until the magnetic tool is removed or the minimum Lower Value is reached.
Page 74
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter options Upper Range Value Adjustment Branch. [URV]. S: Escapes to the Upper Range Value menu. Z: Moves enter options Range Adjustment Branch S: Enter in the Engineering Units adjustment branch [UNIT].
Page 75
Programming Using Local Adjustment Z: Moves enter the options Engineering Units Branch [UNIT]. S: Select bar and comes back to the options tree main branch of complete local adjustment. Z: Moves enter the options Engineering Units Branch [UNIT]. S: Select mbar and comes back to the options tree main branch of complete local adjustment.
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter options Engineering Units Branch [UNIT]. S: Select MPa and comes back to the options tree main branch of complete local adjustment. Z: Moves enter options Engineering Units Branch [UNIT].
Page 77
Programming Using Local Adjustment PRESSURE TRIM BRANCH [TRIM] Z: Moves enter 0 PSWRD and ESC PSWRD. S: This function is protected by a "password," when prompted 0 PSWD, enter the password. The password code is entered by inserting and removing the magnetic tool twice in (S). The password value is changed from 0 to 1.
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter TRIM Branch. S: Enters in the configuration’s branch Upper Pressure Trim. Upper Z: Moves enter Upper Pressure TRIM Branch (UPPER). S: Sets the transmitter internal reference increasing to...
Page 79
Programming Using Local Adjustment CONF OPER DAMP Funct Address CONF DAMP Addr Linear LCD1 Sqrt DAMP Addr Save Save Esc Funct Esc DAMP Esc INC Press LCD2 Press LCD3 Press ESC LCD Figure 5.7 – Local Adjustment Configuration Tree CONFIGURATION BRANCH [CONF] Z: Moves enter main branch options of complete local adjustment tree.
Page 80
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter Damping Time Branch options. S: Increases the damping time constant until the magnetic tool is removed or DAMP 128 seconds are reached. Z: Moves enter Damping Time Branch options.
Page 81
Programming Using Local Adjustment Z: Moves enter Configuration Branch options [CONF]. S: Enter the Display Branch [LCD]. Z: Moves enter options: LCD1, LCD2, LCD3 e ESC LCD. S: Enter the Display 1 Branch [LCD1]. LCD1 Z: Moves enter variable to be indicated as primary display.
Page 82
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter options: LCD1, LCD2, LCD3 e ESC LCD. S: Enter the Display 2 Branch [LCD2]. LCD2 Z: Moves enter variable to be indicated in the Display 2. S: Select the current in mA [ImA].
Page 83
Programming Using Local Adjustment Z: Moves enter options: LCD1, LCD2, LCD3 e ESC LCD. S: Enter the Display 3 Branch [LCD3]. LCD3 Z: Moves enter variable to be indicated in the Display 3. S: Select the output in mA [ImA]. Z: Moves enter variable to be indicated in the Display 3.
Page 84
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter options: LCD1, LCD2, LCD3 e ESC LCD. S: Escapes LCD branch and comes back Configuration branch [CONF]. Z: Moves enter Configuration Branch options [CONF]. S: Enter in Address Branch.
Programming Using Local Adjustment Operation [OPER] ® This adjustment option is applicable to the LD400 HART configured in the Controller mode. It allows the control state to be changed from Automatic to Manual and vice versa, and also to adjust the Setpoint and Manipulated Variable values.
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter 0 PSWRD and ESC PSWRD. PSWRD S: Escapes the PSWRD Branch and comes back the Operation Tree [OPER]. Z: Moves enter Operation Branch options. S: Escapes Operation Tree Branch [OPER].
Page 87
Programming Using Local Adjustment Z: Moves enter 0 PSWRD and ESC PSWRD. S: This function is protected by a "password," when prompted 0 PSWD, enter the password. The password code is entered by inserting and removing the magnetic tool twice in (S). The password value is changed from 0 to 1. After entering the "password," PSWRD you can move around the options Trim Branch using (Z).
® LD400 HART – Operation and Maintenance Instruction Manual Z: Moves enter Operation Branch options [OPER]. S: Enter in the Manipulated Variable adjustment branch [MV]. Z: Moves enter increase or decrease Setpoint value, save or escape. S: Increases the control output until the magnetic tool is removed or the upper output limit is reached.
Should the sensor eventually require maintenance, it may not be changed on the field. In this case, the possibly damaged sensor should be returned to SMAR for evaluation and, if necessary, repair. Refer to the "Returning Materials" item at the end of this Section.
® LD400 HART – Operation and Maintenance Instruction Manual ERROR MESSAGES POTENTIAL SOURCE OF PROBLEM • Temperature out of operating limits. SV OUT OF LIMITS • Temperature sensor damaged. • Pressure out of operation limits; • PV OUT OF LIMITS Sensor damaged or sensor module not connected;...
Page 91
Maintenance Power Supply • ® Check output of power supply. The voltage at the LD400 HART terminals must be between 12 and 50 Vdc, and ripple less than 500 mV. Electronic Circuit Failure • Locate the failure by alternately testing the transmitter circuit and the interface with spare parts.
Check the connection (flat cable, male and female connectors). Type of Sensor Connected to the Main Board ® Check if the sensor connected to the main board is the one specified for the LD400 HART model: Sensor type shall be hyper - High Performance. ...
Page 93
Maintenance replaced. The oscillating circuit is a part of the sensor and the replacement of one implies replacing the other. To remove the sensor from the electronic housing, the electrical connections (in the field terminal side) and the main board connector must be disconnected. Loosen the hex screw (7) and carefully unscrew the electronic housing from the sensor, observing if the flat cable is not excessively twisted.
Maintenance Figure 6.2– Sensor Rotation Stopper Electronic Circuit To remove the circuit board (6), loosen the two screws (5). WARNING The board has CMOS components, which may be damaged by electrostatic discharges. Make sure that these components will be handled by trained people that know the right handling procedures.
® LD400 HART – Operation and Maintenance Instruction Manual Figure 6.3 – Backup Ring Mounting Procedure for tightening the flange screws Tighten one nut till the flange seats; Tighten the nut diagonally across with a torque of 2.5 to 3 Kgfm;...
If it becomes necessary to return the transmitter and/or configurator to Smar, simply contact our office, informing the defective instrument's serial number, and return it to our factory. In order to speed up analysis and solution of the problem, the defective item should be returned with the Service Request Form (SRF –...
® LD400 HART – Operation and Maintenance Instruction Manual Ordering Code MODEL DIFFERENTIAL , FLOW, GAGE, ABSOLUTE AND HIGH STATIC PRESSURE SENSOR 400-0837 Sensor Module Range LIMITS Turn Down Type Unit Unit3 Diferential (10) mbar Diferential and Flow mbar Diferential and Flow...
Page 101
Maintenance MODEL LEVEL SENSOR 400-0837 Smart Pressure Transmitter RANGE LIMITS Turn Down TYPE Unit Min Max Unit Level -500 mbar Note: The range can be extended up to 0.75 LRL and 1.2 URL with Level -250 -2500 2500 mbar small degradation of accuracy. The upper range value must be limited to Level -2500 2500...
Page 102
(12) Only enable for flange ANSI B16.5. Not applicable for vacuum service. (13) Not available for flange JIS 2202. Drain/Vent not applicable. (14) For this option consult Smar. O’Ring should be Viton or Kalrez. (15) Effective for hydrogen migration processes Maximum pressure 24 bar.
Page 103
Maintenance MODEL SENSOR FOR SANITARY PRESSURE TRANSMITTER 400-0837 Sensor Module Range Limits Turn Down COD. TYPE Unit Unit Sanitary -500 mbar Note: The range can be extended up to 0.75 LRL and 1.2 URL with Sanitary -250 -2500 2500 mbar small degradation of accuracy.
Page 104
® LD400 HART – Operation and Maintenance Instruction Manual 400-0837 Continued from sanitary sensor main code COD. Process Connections DN25 DIN 11851 – WITH EXTENSION/316 SST DN40 DIN 11851 - WITH EXTENSION/316 SST DN40 DIN 11851 – 316 SST THREAD DN50 DIN 11851 - WITH EXTENSION/316 SST...
Maintenance ® HART Special Units UNIT VARIABLE CODE DESCRIPTION O (68ºF) inches of water at 68 degrees F inHg (0ºC) inches of mercury at 0 degrees C O (68ºF) feet of water at 68 degrees F millimeters of water at 68 degrees F (68ºF) mmHg (0ºC) millimeters of mercury at 0 degrees C...
Page 106
® LD400 HART – Operation and Maintenance Instruction Manual UNIT VARIABLE CODE DESCRIPTION ft/s feet per second meters per second in/s inches per second ELOCITY in/min inches per minute ft/min feet per minute meters per hour ºC degrees Celsius ºF...
Page 107
Maintenance UNIT VARIABLE CODE DESCRIPTION centistokes ISCOSITY centipoises newton meter decatherm deka therm ft-lb foot pound force NERGY kilo watt hour INCLUDES Mcal mega calorie mega joule british thermal unit grams per second g/min grams per minute grams per hour kg/s kilograms per second kg/min...
Page 108
® LD400 HART – Operation and Maintenance Instruction Manual UNIT VARIABLE CODE DESCRIPTION º/s degrees per second NGULAR rev/s revolutions per second ELOCITY revolutions per minute kilo watt horsepower Mcal/h mega calorie per hour OWER MJ/h mega joule per hour...
Ugevkqp"9" SAFETY INSTRUMENTED SYSTEMS Kpvtqfwevkqp" WARNING LD400 HART ® SIS has the housing cover in red to distinguish them from the standard model. ® LD400 HART SIS is an intelligent pressure transmitter used for differential, absolute, gauge, ® level and flow measurements in safety applications. LD400 HART SIS outputs a 4 to 20 mA DC signal corresponding to the pressure applied.
Page 110
" Uchgv{"Hwpevkqp" ® The LD400 HART SIS transmitter measures the pressure within the safety accuracy and converts it in a 4-20 mA analog output using the selected output transfer function and the output current is treated according to NAMUR NE-43 specification. In case of sensor or circuit failure, the implemented self-diagnoses (software or hardware) drive the output to below 3.6 or above...
Page 111
21.0 mA 3.8 mA 20.5 mA low saturation high saturation Hkiwtg"903"⁄"Cncto"Ngxgnu" Hwpevkqpcn"Uchgv{"Rtqrgtvkgu" ® The Table 7.4 shows the Functional Safety Values obtained for LD400 HART SIS. OPERATION MODE LOW DEMAND TYPE LAMBDA SD (FITS) LAMBDA SU (FITS) LAMBDA DD (FITS) 72.5...
Page 112
SIS Mode ® In the SIS Mode the LD400 HART SIS is enabled to work only as measurement equipment. In this mode no changes on configuration are allowed. Not even the hardware jumpers can be able to change transmitter parameters and only the Hart read commands are permitted in SIS Mode the following applies: ...
Page 113
Uchgv{"Kpuvtwogpvgf"U{uvgou" Functional Specifications MODEL TURN DOWN MODEL TURN DOWN 10:1 20:1 10:1 20:1 20:1 20:1 20:1 20:1 10:1 20:1 20:1 20:1 20:1 20:1 20:1 Turn Down Limits 20:1 10:1 10:1 20:1 10:1 20:1 20:1 20:1 20:1 20:1 20:1 20:1 20:1 20:1 20:1 20:1...
Page 114
Less than 30 seconds for cold start up; Ockpvgpcpeg" ® The maintenance of LD400 HART SIS must be done according to the specifications described in the Section 6. All maintenance services must be done by qualified personnel. Parts replacements must be supplied by Smar.
Use shielded, twisted-pair cable for powering the instrument and signal wiring. Keep the shield insulated at the instrument side, connecting the other one to the ground. The EC declarations of conformity for all applicable European directives for this product can be found at www.smar.com. Hazardous Locations Certifications NOTE The IP68 sealing test (immersion) was performed at 1 bar for 24 hours.
For maintaining the explosion protection, the manual that accompany the products shall be considered. Type Designation: LD400-***-X1*-*****-***-X2**-X3X4D2*/* X1 = Communication Protocol (H - HART® & 4 to 20 mA) X2 = Electrical connection (0 = ½ - 14NPT; A = M20x1,5)
Page 117
For maintaining the explosion protection, the manual that accompany the products shall be considered. Type Designation: LD400-***-X1*-*****-***-**-****X2*-X3X4D2***/* X1 = Communication Protocol (H - HART® & 4 to 20 mA) X2 = Electrical connection (0 = ½ - 14NPT; A = M20x1,5)
Page 118
For maintaining the explosion protection, the manual that accompany the products shall be considered. Type Designation: LD400-***X1*-*****-**-****-***X2*-X3X4D2/* X1 = Communication Protocol (H - HART® & 4 to 20 mA) X2 = Electrical connection (0 = ½ - 14NPT; A = M20x1,5)
For maintaining the explosion protection, the manual that accompany the products shall be considered. Type Designation: LD400-***-X1*-****-X2**-X3X4D2*/********* X1 = Communication Protocol (H - HART® & 4 to 20 mA) X2 = Electrical connection (0 = ½ - 14NPT; A = M20x1,5)
Page 120
® – Operation and Maintenance Instruction Manual LD400 HART Identification of Intrinsically Safe and Explosion Proof for saline atmospheres:...
Page 121
Certification Information Identification of Intrinsically Safe and Explosion Proof for gas and steam:...
Page 122
® – Operation and Maintenance Instruction Manual LD400 HART Identification of ATEX approval:...
(Please, describe the observed behavior, if it is repetitive, how it reproduces, etc.) OBSERVATIONS USER INFORMATION Company: Contact: Title: Section: Phone: Extension: E-mail: Date: Signature: For warranty or non-warranty repair, please contact your representative. Further information about address and contacts can be found on www.smar.com/contactus.asp.
Need help?
Do you have a question about the LD400 and is the answer not in the manual?
Questions and answers