Troubleshooting - EIP CD100E Owner's Manual

Industrial dehumidifier
Table of Contents

Advertisement

S
YMPTOM
Unit inoperative
(no red light)
Little or no airflow
Little or no water
extraction
Little or no defrost
when required
Unit vibrates
excessively

TROUBLESHOOTING

C
1. No power to unit
1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring
5. Fuse blown
1. Insufficient air movement
2. Compressor fault
3. Loss of refrigerant gas
4. Blocked filter dryer
1. Faulty Timer
2. Faulty bypass timer
1. Loose compressor mounts
damaged
2. Damaged Fan
Spare parts available online
www.EIPLDIRECT.com
Page 10 of 16
AUSE
1. Check the power supply
and fuse
1. Tighten fan
2. Replace the fan motor
3. See Routine Maintenance
Section
4. Check the wiring diagram
to find fault and repair
5. Replace the fuse
1. Check all of the above
2. Contact the Factory
Service Center
3. Contact the Factory
Service Center
4. Contact the Factory
Service Center
1. Contact the Factory
Service Center
2. Contact the Factory
Service Center
1. Tighten the nuts on the
compressor mounts
2. Remove obstruction
Drawing : - TPC262
Issue
: - 5
Date
: - 05/01/12
R
EMEDY