2.3.3 Connecting the Control Terminals

Table 2.3.3 lists the functions of the control circuit terminals. A control circuit terminal should be connected according
to its function setting.
Table 2-3-3
Terminal
Classification
Symbol
Analog input
13
12
V2
C1
11
Data subject to change without notice 7/07. © 2007 GE Drives
Terminal Name
Potentiometer power supply
Voltage input
Voltage input
supplied from an external circuit.
Current input
Analog input common
Function
Used for +10V DC power supply for frequency setting POT
(resistance of 1 to 5k Ohms)
1. Frequency is set according to the analog input voltage
supplied from an external circuit.
- 0 to +10V DC / 0 to 100%
- Reversible operation using positive and negative signals:
0 to +/- 10V DC / 0 to 100%
- Reverse operation: +10 to 0V DC / 0 to 100%
2. Input feedback signal for PID control is input.
3. The analog input value from the external circuit is used
for torque control
* Input resistance: 22 k Ohms
¨ Frequency is set according to the analog input voltage
- 0 to +10V DC/0 to 100%
- Reverse operation: +10 to 0V DC/0 to 100%
* Use only one terminal - V2 or C1 Exclusively
* Input resistance: 22 k Ohms
1. Frequency is set according to the analog input current supplied
from an external circuit.
- 4 to 20mA DC / 0 to 100%
- Reverse operation: 20 to 4mA DC / 0 to 100%
2. The feedback signal for PID control is input.
3. PTC thermistor input
* Use only one terminal - V2 or C1 Exclusively
* Input resistance: 250 Ohms
* PTC switch is off when PTC function is not used
Common terminal for analog input signals
2-11