Torque limit 2/torque limit 1
Value 14: Frequency setting 2/frequency setting 1. This
function switches the torque limit value set with function
codes F40, F41, E16, and E17, using an external digital
input signal.
Input Signal
Selected Torque Limit Value
14
off
F40 DRV TRQ1
F41 BRK TRQ1
on
E16 DRV TRQ2
E17 DRV TRQ2
Switching operation from line drive
(60Hz)(SW60)/(50Hz)(SW50)
Value 15, 16: Motor operation can be switched from 60
Hz/50 Hz commercial power to drive operation without
stopping the motor by switching the external digital input
signal.
Input Signal
Function
16
off > on
Drive operation to line operation (60 Hz)/(50 Hz)
on > off
Line operation to drive operation (60 Hz)/(50 Hz)
Following a momentary power failure, if the digital input
signal goes off, 50 or 60 Hz (according to the input
signal) is output after the restart waiting time (function
code H13). The motor is then directed to drive opera-
tion.
UP command (UP)/DOWN command (DOWN)
Value 17, 18: When an operation command is input (on),
the output frequency can be increased or decreased
using an external digital input signal.
The change ranges from 0 to maximum frequency.
Operation in the opposite direction, of the operation
command is not allowed.
Combination
of Input Signals
18
17
off
off
off
on
on
off
on
on
There are the two types of UP/DOWN operations as
shown below. Select the desired type by setting the
frequency (F01 or C30).
Related Functions
F40-F41, E16-E17
Setting Range
DRV 20 to 200% ,999
BRK0, 20 to 200%, 999
Selected Function
(when operation command is on)
Holds the output frequency
Increases the output frequency
according to the acceleration time
Decreases the output frequency
according to the deceleration time
Holds the output frequency
Edit permission command (data change
permission)(WE-KP) (data protection)
Value 19: This function allows the data to be changed
only when input is received from an external signal,
thereby preventing function code data changes.
Selected Function
19
Prohibit data changes
off
Allow data changes
on
Note: If a terminal is assigned the value 19, the data
cannot be changed. To change data, turn the terminal on
and change its setting to another number.
PID control cancellation (Hz/PID)
Value 20: The PID control can be disabled by an external
digital input signal.
Selected Function
Input Signal
[Related Functions: H20-H25]
20
Enable PID control
off
Disable PID control
on
(When the PID control is disabled, the frequency is set
from keypad panel)
Normal operation/inverse
Value 21: Analog input (Terminals 12 and C1) can be
switched between normal and inverse operations using an
external digital input signal.
Selected Function
Input Signal
[Related Function: F01]
21
Normal operation if normal operation is
off
set and vice versa
Inverse operation if normal operation is
on
set and vice versa
Interlock (52-2)
Value 22: When a contactor is installed on the output side
of the drive, the contactor opens at the time of a momen-
tary power failure. This prevents the reduction of the DC
circuit voltage and may prevent the detection of a power
failure and a correct restart operation after power is
recovered. The restart operation, in the event of a
momentary power failure, can be performed effectively
with power failure information provided by an external
digital input signal.
5-20