GE AF-300 P11 User Manual page 146

Table of Contents

Advertisement

Name
Analog I/O Interface Card
Type
OPCG11SAIO
3 analog inputs (2 voltage inputs and 1 current input): Torque limiting value (driving, braking), frquency setting, ratio setting
can be input respectively.
Function
2 analog outputs (1 voltage output and 1 current output): 11 types of data can be output.
Specifications
Input
Output
Connection
diagram
RUN command
Remarks
Data subject to change without notice 7/07. © 2007 GE Drives
Analog signal input (3 points) 32 and 31, 22 and 21, C2 and 21.
Terminal 32: Voltage input (both sides):
Terminal 22: Voltage input (both sides):
Terminal C2: Current input:
For voltage input, power supply terminal for variable resistor (P10) should be connected.
Related function code o22
Analog signal input (2 points) between AO+ and AO-, CS+ and CS-
Terminal AO+: Voltage output: 0 to ±10 VDC, for max. 2 voltmeters, input impedance: 10k ohm
Terminal AO-: Voltage output common.
Terminal CS+: Current output: 4 to 20mAdc, max. 500 ohm
Terminal CS-: Current output common
(Terminal CS- is isloated from terminal 21, 31 and AO-)
Related function code o23
MCCB
or
ELCB
L1/R
L2/S
L3/T
(R0) *
(T0) *
13
12
11
AF-300 P1 1
C1
Y5A
Y5C
Y4
Y3
Y2
Y1
CM
E
PLC
input
FW
D
REV
CM
X1
X2
X3
X4
X5
X6
X7
X8
X9
CM
FM
FM
A
P
DX
B
DX
A
SD
E(G)
* Te rm i na ls [ R0 ] an d [ T0] ar e no t prov id ed f or 1.0 HP or s m aller.
0 to ±10 VDC / 0 to ±100%, input impedance: 22k ohm.
0 to +10 VDC / 0 to +100%, input impedance: 22k ohm.
4 to + 20mADC / 0 to +100%, input impedance: 250k ohm.
U
V
W
30A
30B
30C
VR
32
Voltage input
31
(Both polarity)
( 1k ohm)
VR
22
Voltage input
(Single polarity)
21
(1k ohm)
C2
(+)
(+)
Current input
(-)
AO+
Analog voltmeter
AO-
CS+
Anammeter
CS-
13-3
M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents